2021-06-01 09:12:272020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030396
 ADD: 1900 OKEECHOBEE RD.
 CONT: SISCA CONSTRUCTION
 TEL: 561-686-5545
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. JUNE 01ST/ 2021
 ACTION:
 1) BUILDING PROVISO: 2020FBC-BUILDING CODE. & 2020 W.
 P. B. AMENDMENTS. DURING THE PERMITTING OF THIS
 STRUCTURE THERE WILL BE REQUIRED (3) DIFFERENT FLOOD
 ZONE CERTIFICATES REQUIRED:
  
 (1) COMPLIED. A FLOOD ZONE CERTIFICATE IS REQUIRED AS
 PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED
 FINISH FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE
 107.3.5.1.1 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATION
 CERTIFICATE PROPOSED HEIGHT OF THE BUILDING AND OR
 STRUCTURE.
  
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 .
 2)BUILDING PROVISO. WHEN RACK STORAGE IS OVER 5 FEET 9
 INCHES IN HEIGHT, FIXED/ ANCHORED A SEPARATE PERMIT
 REVIEW AND ASSOCIATED FEES ARE REQUIRED. WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION 105.2(6)
  
 3) BUILDING PROVISO. THIS BUILDING CONTAINS BOLTED AND
 WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO
 PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 4A) BUILDING PROVVISO / DEFERRED SUBMITTALS. SEE LIST
 ON COVERSHEET.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  