| 2021-06-01 09:12:27 | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21030396 |
| | ADD: 1900 OKEECHOBEE RD. |
| | CONT: SISCA CONSTRUCTION |
| | TEL: 561-686-5545 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. JUNE 01ST/ 2021 |
| | ACTION: |
| | 1) BUILDING PROVISO: 2020FBC-BUILDING CODE. & 2020 W. |
| | P. B. AMENDMENTS. DURING THE PERMITTING OF THIS |
| | STRUCTURE THERE WILL BE REQUIRED (3) DIFFERENT FLOOD |
| | ZONE CERTIFICATES REQUIRED: |
| | |
| | (1) COMPLIED. A FLOOD ZONE CERTIFICATE IS REQUIRED AS |
| | PART OF THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED |
| | FINISH FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE |
| | 107.3.5.1.1 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR |
| | COMMERCIAL BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATION |
| | CERTIFICATE PROPOSED HEIGHT OF THE BUILDING AND OR |
| | STRUCTURE. |
| | |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | . |
| | 2)BUILDING PROVISO. WHEN RACK STORAGE IS OVER 5 FEET 9 |
| | INCHES IN HEIGHT, FIXED/ ANCHORED A SEPARATE PERMIT |
| | REVIEW AND ASSOCIATED FEES ARE REQUIRED. WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION SECTION 105.2(6) |
| | |
| | 3) BUILDING PROVISO. THIS BUILDING CONTAINS BOLTED AND |
| | WELDED CONNECTIONS. THE CONTRACTOR IS REQUIRED TO |
| | PROVIDE WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR |
| | PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH |
| | THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR |
| | FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY |
| | CERTIFICATION WILL BE REQUIRED. |
| | THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO |
| | COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS |
| | SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING |
| | INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | |
| | 4A) BUILDING PROVVISO / DEFERRED SUBMITTALS. SEE LIST |
| | ON COVERSHEET. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |