Plan Review Notes
Plan Review Notes For Permit 21030396
Permit Number 21030396
Review Stop P
Sequence Number 1
Notes
Date Text
2021-05-03 16:59:2205/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A5;
 A. THE WATER CLOSET DIAGRAM SHOWS THE PAPER HOLD NOT TO
 CENTER DIMENSION FRONT 7" TO 9" PER THE 2020 FBC ACC
 SEC. 604.7.
  
 B. THE SIDE GRAB BARS ON THE HORIZONTAL ARE TO THE
 CENTER PER THE 2020 FBC ACC SEC. 604.5.1. SIDE WALL.
  
 C. THE WATER CLOSET OF THE WALL SHALL BE 16" TO 18" PER
 THE FBC ACC SEC. 604.2 LOCATION.
  
 D. THE TOILET SEATS NEED TO BE 17" INCHES TO 19" INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 E. THE DOOR SWINGS IN THE CLEAR FLOOR SPACE PLEASE SHOW
 THE TURNING SPACE DIAMETER PER THE 2020 FBC SEC.
 304.3.1 CIRCULAR SPACE.
  
 F. PLEASE REMOVE OR X OUT SHOWER AND ANY OTHER DRAWING
 THAT DO NOT PERTAIN TO THESE PLANS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 G. PLEASE SHOW A DETAIL ON GRAB BAR THAT COMPLIES WITH
 2020 FBC SEC. 609.8 STRUCTURAL STRENGTH.
  
 2. PLEASE PROVIDE A NOTE ON THE PLANS THAT AN RPZ
 BACKFLOW WILL REQUIRES A SEPARATE PERMIT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 3. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  