| Date |
Text |
| 2021-04-13 15:01:23 | 1) THE SUBMITTED ELEVATION CERTIFICATE IT IS ASSUMED |
| | FOR THE EXISTING BUILDING. THE CITY ALSO NEEDS A FLOOD |
| | CERTIFICATE FOR THE PROPOSED NEW LATERAL ADDITION. |
| | IMPROVEMENT VALUE OF THE EXISTING STRUCTURE IS |
| | $2,263,265.00 DOLLARS (TAKEN FROM PALM BCH. COUNTY |
| | PROPERTY APPRAISERS WEBSITE). THE PROPOSED VALUE OF THE |
| | ADDITION IS $1,050,000.00 OF DOLLARS THE PERMIT VALUES |
| | WITHIN THE LAST 5 YEARS $27,100.00 OF VALUE TOTAL VALUE |
| | OF $1,077,100.00 LESS THAN ? OF IMPROVEMENT VALUE OF |
| | $1,131,632.50 DOLLARS. |
| | |
| | SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR |
| | FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR, |
| | RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE |
| | CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR |
| | EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT |
| | OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF |
| | NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE. |
| | THE ORIGINAL BUILDING WAS BUILT, C/OED IN 1969. |
| | PRE-FIRM. THE FIRST FIRM MACH 01/ 1979. CURRENT FLOOD |
| | ZONE AE/ BFE: 12.7. IN NAVD88. |
| | |
| | TAKEN FROM FEMA BULLITIN SUBSTANIAL IMPROVEMENT AND |
| | REPAIR SUBSTANIAL REPAIR. PLEASE REVIEW TABLE 6-1A, |
| | COMPLIANCE MATRIX (A ZONES). THE TYPE OF WORK TO BE |
| | CONSIDERED IS LATERAL ADDITION NOT SI (SUBSTANIAL- |
| | IMPROVEMENT), & THE EXISTING BUILDING TO BE CONSIDERED |
| | PRE-FIRM. ADDITION NOT REQUIRED TO COMPLY. |
| | |
| | PLEASE NOTE AN ADDITIONAL DOLLAR AMOUNT OF $ 54,532. 50 |
| | WOULD MAKE THIS A SUBSTANTIAL IMPROVEMENT, |
| | REHABILITATION (RENOVATION OR REMODEL) AND A |
| | SUBSTANTIAL IMPROVEMENT, BUILDING (THE ORIGINAL |
| | BUILDING AND ADDITION) WOULD REQUIRED TO COMPLY, SEE |
| | THE REQUIREMENT FOR DRY FLOOD PROOFING . |
| | |
| | PLEASE PROVIDE A COST BREAK DOWN FOR THE NEW ADDITION. |
| | THE COST BREAK DOWN WILL INCLUDE THE TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING, |
| | MECHANICAL, INTERIOR FINISHES, (EXCAVATION AND BACKFILL |
| | FOR BUILDINGS), ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. THIS DOCUMENTATION IS KEPT FOR THE FUTURE |
| | FEMA AUDIT. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |