| Plan Review Notes For Permit 21030396 |
| Permit Number |
21030396 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-05-04 07:28:13 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21030396 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE | | | ENTIRE STRUCTURE. FBC EC C402 | | | | | | 2) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS FOR EACH RTU AND THE AHU. FBC EC C403.2.1 | | | AND FBC M 312.1 | | | | | | 3) PLEASE SHOW THE CONDENSATION PIPING AND THE | | | TERMINATION LOCATION FOR THE MINI-SPLIT. FBC M 307.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|