Plan Review Notes
Plan Review Notes For Permit 21030396
Permit Number 21030396
Review Stop B
Sequence Number 1
Notes
Date Text
2021-04-13 14:21:472020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030396
 ADD: 1900 OKEECHOBEE RD.
 CONT: SISCA CONSTRUCTION
 TEL: 561-686-5545
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: TUES. APRIL 06TH/ 2021
 ACTION: DENIED
  
 1) THE SUBMITTED ELEVATION CERTIFICATE IT IS ASSUMED
 FOR THE EXISTING BUILDING. THE CITY ALSO NEEDS A FLOOD
 CERTIFICATE FOR THE PROPOSED NEW LATERAL ADDITION.
 IMPROVEMENT VALUE OF THE EXISTING STRUCTURE IS
 $2,263,265.00 DOLLARS (TAKEN FROM PALM BCH. COUNTY
 PROPERTY APPRAISERS WEBSITE). THE PROPOSED VALUE OF THE
 ADDITION IS $1,050,000.00 OF DOLLARS THE PERMIT VALUES
 WITHIN THE LAST 5 YEARS $27,100.00 OF VALUE TOTAL VALUE
 OF $1,077,100.00 LESS THAN ? OF IMPROVEMENT VALUE OF
 $1,131,632.50 DOLLARS.
  
 SUBSTANIAL IMPROVEMENT. SECTION 94-546 PROVISIONS FOR
 FLOOD HAZARD REDUCTION. (A)(3) ANY ALTERATION, REPAIR,
 RECONSTRUCTION, OR IMPROVEMENTS TO A PROPERTY WHICH THE
 CUMULATIVE COST FOR ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 % OF THE BUILDING VALUE AT THE COMMENCEMENT
 OF THE FIVE YEAR PERIOD SHALL MEET THE REQUIREMENTS OF
 NEW CONSTRUCTION AS CONTAINED IN THIS ARTICLE.
 THE ORIGINAL BUILDING WAS BUILT, C/OED IN 1969.
 PRE-FIRM. THE FIRST FIRM MACH 01/ 1979. CURRENT FLOOD
 ZONE AE/ BFE: 12.7. IN NAVD88.
  
 TAKEN FROM FEMA BULLITIN SUBSTANIAL IMPROVEMENT AND
 REPAIR SUBSTANIAL REPAIR. PLEASE REVIEW TABLE 6-1A,
 COMPLIANCE MATRIX (A ZONES). THE TYPE OF WORK TO BE
 CONSIDERED IS LATERAL ADDITION NOT SI (SUBSTANIAL-
 IMPROVEMENT), & THE EXISTING BUILDING TO BE CONSIDERED
 PRE-FIRM. ADDITION NOT REQUIRED TO COMPLY.
  
 PLEASE NOTE AN ADDITIONAL DOLLAR AMOUNT OF $ 54,532. 50
 WOULD MAKE THIS A SUBSTANTIAL IMPROVEMENT,
 REHABILITATION (RENOVATION OR REMODEL) AND A
 SUBSTANTIAL IMPROVEMENT, BUILDING (THE ORIGINAL
 BUILDING AND ADDITION) WOULD REQUIRED TO COMPLY, SEE
 THE REQUIREMENT FOR DRY FLOOD PROOFING .
  
 PLEASE PROVIDE A COST BREAK DOWN FOR THE NEW ADDITION.
 THE COST BREAK DOWN WILL INCLUDE THE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, PLUMBING,
 MECHANICAL, INTERIOR FINISHES, (EXCAVATION AND BACKFILL
 FOR BUILDINGS), ARCHITECTURAL AND DESIGN FEES,
 MARKETING COST, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. THIS DOCUMENTATION IS KEPT FOR THE FUTURE
 FEMA AUDIT.
  
 2) THE LIFE SAFETY SHEET LS.1:
 2A) THE BUILDING CLASSIFICATION LIST THE CONSTRUCTION
 TYPE AS II-B FULLY SPRINKLERED AND ALLOWED V-B. PLEASE
 NOTE THIS IS A ADDITION TO AN EXISTING BUILDING. THE
 EXISTING BUILDING SQUARE FOOTAGE IS 3025 OFFICE AND 30,
 885 WAREHOUSE OR 33,910 SQ. FT. + 14,950 SQ. FT. =
 48,860 TOTAL SQ. FT. THE MINIMUM ALLOWABLE WOULD BE
 EITHER TYPE V-A SPRINKLERED OR III-B SPRINKLERED.
  
 2B) OCCUPANT LOAD THE ORIGINAL BUILDING NEEDS TO BE
 APPLIED AS WELL. THE PROPERTY APPRAISERS OFFICE LIST
 3025 SQ. FT. AS OFFICE SPACE/ BUSINESS OCCUPANCY.
 PLEASE NOTE IN THE 2020 FBC-B TABLE 1004.1.2 THE FACTOR
 TO BE TAKEN FOR BUSINESS OCCUPANCY IS NOW 150 SQ. FT./
 OCCUPANT. UPDATE OCCUPANT LOADS FOR THE EXISTING
 BUILDING PLUS ADDITION.
  
 2C) OCCUPANT LOAD SHOWS DECIMALS OR PORTIONS OF
 OCCUPANTS. FOR THE MEANS OF EGRESS, YOU ALWAYS ROUND UP
 TO THE NEXT FULL NUMBER FOR EACH CATEGORY. BOAF
 (BUILDING OFFICIALS ASSOCIATION OF FLORIDA) INFORMAL
 INTERPRETATIONS.
  
 2D) PLEASE PROVIDE THE RACK STORAGE LAYOUT ON THE LIFE
 SAFETY PLAN FOR EXIT DIRECTIONAL LIGHT REQUIREMENTS
 SIGHT LINES. 2020 FBC-B 1013.1 WHERE REQUIRED.
  
 2E) WHEN RACK STORAGE IS OVER 5 FEET 9 INCHES IN
 HEIGHT, FIXED/ ANCHORED A SEPARATE PERMIT REVIEW AND
 ASSOCIATED FEES ARE REQUIRED. WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 105.2(6)
  
 3) NOTE CHANGED ON 4/14/2021. THIS BUILDING CONTAINS
 BOLTED AND WELDED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 4A) THE COVER SHEET LIST ITEMS THAT WILL NEED SHOP
 DRAWING, THEY DO NOT REQUEST THESE ITEMS TO BE DEFERRED
 SUBMITTALS INCOMPLIANCE WITH 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 4B) PRODUCT APPROVALS REQUIRED. COMPONENTS & CLADDING.
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP CURBS, ROOF TOP RTU
 UNITS.
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 5) COMPONENT & CLADDING PRESSURE ARE FOUND ON SHEET
 S-004 AND ARE IN VULT PRESSURES FOR ZONES 1-5. PLEASE
 PROVIDE THE PRESSURES IN VASD SINCE ALL PRODUCT
 APPROVALS FOR COMPONENTS AND CLADDING ARE IN VASD.
 THANK YOU. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6A) SHEET M-2 THE MECHANICAL ROOF TOP PLAN 1 SHOWS 4
 RTU UNITS ON THE ROOF. THE PLAN DOES NOT INDICATE HOW
 YOU ARE GOING TO GET UP ONTO THE ROOF TO SERVICE THE
 EQUIPMENT.
  
 2017 FBC-M 306.5 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING ACCESS
 OR APPLIANCES ARE LOCATED ON AN ELEVATED STRUCTURE OR
 THE ROOF OF A BUILDING SUCH THAT PERSONNEL WILL HAVE TO
 CLIMB HIGHER THAN 16 FEET (4877 MM) ABOVE GRADE TO
 ACCESS SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR
 EXTERIOR MEANS OF ACCESS SHALL BE PROVIDED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES (762 MM) IN HEIGHT OR WALKING ON ROOFS
 HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN 12
 UNITS HORIZONTAL (33-PERCENT SLOPE). SUCH ACCESS SHALL
 NOT REQUIRE THE USE OF PORTABLE LADDERS. WHERE ACCESS
 INVOLVES CLIMBING OVER PARAPET WALLS, THE HEIGHT SHALL
 BE MEASURED TO THE TOP OF THE PARAPET WALL.
  
 6B) THE PLANS ARE MISSING COMPLIANCE WITH:
 2020 FBC-B 1011.16 LADDERS. PERMANENT LADDERS SHALL NOT
 SERVE AS A PART OF THE MEANS OF EGRESS FROM OCCUPIED
 SPACES WITHIN A BUILDING. PERMANENT LADDERS SHALL BE
 PERMITTED TO PROVIDE ACCESS TO THE FOLLOWING AREAS:
 1.SPACES FREQUENTED ONLY BY PERSONNEL FOR MAINTENANCE,
 REPAIR OR MONITORING OF EQUIPMENT.
 5.NONOCCUPIED ROOFS THAT ARE NOT REQUIRED TO HAVE
 STAIRWAY ACCESS IN ACCORDANCE WITH SECTION 1011.12.1.
 6.LADDERS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 SECTION 306.5 OF THE FLORIDA BUILDING CODE, MECHANICAL.
  
 6C) IF THE SHIPS LADDER IS BUILT IN THE INSIDE OF THE
 BUILDING THEN A ROOF HATCH WOULD ALSO BE REQUIRED. ROOF
 TOP HATCHES/ ROOF ACCESS/ 2020 FBC-B 1011.12.2. IN
 BUILDINGS THAT DO NOT HAVE AN OCCUPIED ROOF SHALL BE
 PERMITTED TO BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN
 16 SQUARE FEET IN AREA AND HAVING A MINIMUM DIMENSION
 OF 2 FEET.
  
 7) THIS REQUIREMENT IS IF THERE IS NO RESIDENT
 INSPECTOR ON THE JOB. SHEET S-201 THE ROOF FRAMING PLAN
 DOES NOT SHOW THE NECESSARY ADDITIONAL FRAMING FOR THE
 ROOF TOP CURBS. SHEET S-403 DOES PROVIDE NOTES FOR
 EXISTING ROOF TOPS BUT NOT THE WELDING REQUIREMENTS FOR
 ADDITIONAL ROOF FRAMING MEMBERS, TYPES OF WELDS AND
 SIZE AND SPACING. THE CONTRACTOR IS REQUIRED TO PROVIDE
 WELD PROCEDURE SPECIFICATIONS & WELDER OPERATOR
 PERFORMANCE QUALIFICATION RECORDS IN ACCORDANCE WITH
 THE REFERENCED STANDARDS AT TIME OF INSPECTION FOR
 FIELD WIELDING, ON THE JOB-SITE WIELDING. THIRD PARTY
 CERTIFICATION WILL BE REQUIRED. REPORTS SUBMITTED TO
 BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  