| 2021-03-11 15:00:17 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) REVISE NOTE ON SURVEY. THE GENERATOR EXHAUST IS | | | REQUIRED TO BE 10 FEET FROM OPENINGS INTO A BUILDING. | | | FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 2) SUBMIT GENERATOR SPECIFICATIONS AND CUT SHEETS. FBC | | | AMENDMENTS 107.2.1 | | | | | | 3) SUBMIT GENERATOR PAD AND ANCHORING DETAILS, FBC | | | AMENDMENTS 107.2.1 | | | | | | | | | | | | | | | |
|