| Plan Review Notes For Permit 21030347 |
| Permit Number |
21030347 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-17 13:28:35 | PLAN REVIEW / ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1.PROVIDE AVAILABLE SHORT CIRCUT CURRENT AT METER. SEE | | | COMMENT UNDER 21020567 | | | FBC 107 AIC RATING OF SERVICE DISCONNECT AND PANEL NEC | | | 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|