2021-04-14 17:46:121ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21030333
 4/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-00: THE DRAWING INDEX SHOWS MANY
 ARCHITECTURAL PLANS THAT HAVE NOT BEEN UPLOADED FOR
 REVIEW. PLEASE PROVIDE THE PLANS AND ALSO REVISE THE
 INDEX TO INCLUDE THE MEP PLANS- SECTION 107.2.1 WPB.
  
 2) A-00 & P-PLANS: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3 FBC P.
 PROVIDE A SCHEDULE THAT LISTS THE NUMBER OF REQUIRED
 AND THE NUMBER OF PROVIDED FIXTURES FOR THE A2
 OCCUPANCY. PLEASE REFER TO SECTION 410.4 FBC P AND NOTE
 THAT A DRINKING FOUNTAIN IS REQUIRED UNLESS IT IS NOTED
 ON THE PLAN THAT DRINKING WATER WILL BE PROVIDED FREE
 OF CHARGE.
  
 3) ACCESSIBLE PLUMBING FIXTURE DETAILS REQUIRED PER FBC
 ACC:
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 G) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 H) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 I) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 4) P-1: BASED ON SECTION 1003.3.1 FBC P. THE HAND SINKS
 AND FLOOR SINK UNDER THE ICE MACHINE SHALL NOT DRAIN
 INTO THE GREASE WASTE LINE- PLEASE CORRECT THE PLAN.
  
 5) P-1: HYDROMECHANICAL GREASE INTERCEPTORS SHALL BE
 SIZED IN ACCORDANCE WITH ASME A112.14.3, ASME
 A112.14.4, ASME A112.14.6, CSA B481.3 OR PDI G101-
 SECTION 1003.3.5 FBC P. PLEASE INDICATE THE SIZING
 METHOD USED AND HOW THE NUMBER OF MEALS AND LBS. PER
 MEAL WERE DETERMINED.
  
 6) P-1: THE SAMPLING PORT DETAIL SHOWING A SANITARY
 CROSS WITH SUMP WHICH IS NOT ACCEPTABLE. PLEASE PROVIDE
 A SAMPLING PORT DETAIL IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.3.5 FBC P.
  
 7) P-1 & P-3: PLEASE PROVIDE A PLUMBING FIXTURE
 SCHEDULE LISTING THE MAKES AND MODELS OF THE ACCESSIBLE
 TOILET ROOM FIXTURES- SECTIONS 412, 419, & 425 FBC P.
  
 8) P-1 & P-3: PROVIDE A KITCHEN EQUIPMENT PLAN AND
 CORRELATING EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB.
  
 9) P-2: THE BRANCH DRAIN CONNECTIONS FROM THE FLOOR
 SINKS BELOW THE 3-COMPARTMENT SINK AND ICE MAKER ARE
 NOT SHOWN IN THE SANITARY ISOMETRIC- SECTION 704 FBC P.
  
 10) P-1 & P2: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES IN COMPLIANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. IF MIXING VALVES ARE USED UNDER
 THE SINKS PLEASE PROVIDE AN INSTALLATION DETAIL.
  
 11) P-3: PROVIDE THE MAKE AND MODEL AND EFFICIENCY
 RATING OF THE NEW WATER HEATER- TABLE C404.2 FBC EC.
  
 12) P-3: PROVIDE AN INDIRECT WASTE DETAIL FOR THE FLOOR
 SINKS- SECTIONS 802.1.1 & 802.3.
  
 13) P-1: PROVIDE THE TYPES OF FLOOR AND WALL, SURROUND
 MATERIAL TO BE USED AT THE MOP SINK. PLEASE NOTE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT
 LESS THAN 4 FEET SHALL BE PROVIDED- SECTION 1210.2.2
 FBC B.
  
 14) P-1: THE PLAN SHOWS AN LP TANK BLOCKING ACCESS TO
 THE SANITARY DRAIN/SEWER JUNCTION CLEANOUT- SECTION
 708.1.10 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER