2021-04-08 12:29:241ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030333
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ATTACH A STATEMENT ON THE MECHANICAL PLANS
 THAT THE KITCHEN HOOD, GREASE DUCT AND MAKEUP AIR WILL
 BE SUBMITTED UNDER A SEPARATE PERMIT AND MECHANICAL
 REVIEW.
  
 2) PLEASE ATTACH A STATEMENT ON THE MECHANICAL PLANS
 THAT THE REFRIGERATION WILL BE SUBMITTED UNDER A
 SEPARATE PERMIT AND PLAN REVIEW.
  
 3) AS THIS IS A CHANGE OF USE FROM MERCANTILE TO AN A-2
 PLEASE PROVIDE A COMPLETE MECHANICAL SIZING
 CALCULATION. FBC EC C403.2.1
  
 4) SHEET M-1: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE 2020 FBC M 403.3.1.1 AND
 TABLE 403.3.1.1
  
 5) SHEET M-1: RTU-2 INDICATES A MAXIMUM 2000 CFM OF
 SUPPLY AIR, CALCULATING THE TOTAL OF EACH SUPPLY GRILLE
 IS 3475 CFM. PLEASE MAKE SURE THE TWO MATCH. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  