Plan Review Notes
Plan Review Notes For Permit 21030333
Permit Number 21030333
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-15 08:46:341ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030333
 4/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA 58- 2017
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: CLARIFY THE NUMBER OF LP TANKS TO
 BE INSTALLED. P-1 SHOWS 3 TANKS WITH 2 MANIFOLDED
 TOGETHER, P-2 SHOWS 2 TANKS- SECTION 107.2.1 WPB.
  
 2) P-1 & P-2: INDICATE THE GALLON SIZES OF THE TANKS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 5.2.1.1 NFPA 58.
  
 3) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE
 REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH
 THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW
 HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND
 WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58.
  
 4) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE
 CLEARANCE DISTANCES FOR THE TANKS TO THE BUILDING- SEE
 SECTIONS 6.4.3.2 (A) & (B) AND TABLE 6.4.1.1 NFPA 58.
  
 5) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE
 CLEARANCE DISTANCES FOR THE TANK RELIEF VALVES TO THE
 REAR DOOR OPENING, MECHANICAL AIR INTAKES, AND EXTERIOR
 SOURCES OF IGNITION- SECTIONS 6.4.4.3 & 6.4.4.4 AND
 TABLE 6.4.4.3 NFPA 58.
  
 6) P-1 & P-2: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1
 NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE
 REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A
 2 PSI REGULATOR IS REQUIRED FOR THE 11 IN.WC SYSTEM.
 PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATOR.
 7) P-1: REFER TO SECTION 6.10.1.7 NFPA 58 AND INDICATE
 THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE RELIEF
 VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL AIR
 INTAKES, AND ANY SOURCE OF IGNITION.
  
 8) P-1 & P-2: SUBMIT MANUFACTURER'S DATA SHEETS FOR THE
 COOKING APPLIANCES SHOWING APPLIANCE LISTINGS, BTU
 CAPACITIES, AND INPUT PRESSURES- SECTION 623.1 FBC FG.
  
 9) P-1 & P-2: INDICATE HOW COMBUSTION AIR WILL BE
 PROVIDED TO THE COOKING APPLIANCES AND PROVIDED
 CALCULATIONS- SECTION 304.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  