| Date |
Text |
| 2021-04-15 08:46:34 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21030333 |
| | 4/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | NFPA 58- 2017 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P-1 & P-2: CLARIFY THE NUMBER OF LP TANKS TO |
| | BE INSTALLED. P-1 SHOWS 3 TANKS WITH 2 MANIFOLDED |
| | TOGETHER, P-2 SHOWS 2 TANKS- SECTION 107.2.1 WPB. |
| | |
| | 2) P-1 & P-2: INDICATE THE GALLON SIZES OF THE TANKS |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION |
| | 5.2.1.1 NFPA 58. |
| | |
| | 3) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE |
| | REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL |
| | SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH |
| | THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW |
| | HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND |
| | WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58. |
| | |
| | 4) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE |
| | CLEARANCE DISTANCES FOR THE TANKS TO THE BUILDING- SEE |
| | SECTIONS 6.4.3.2 (A) & (B) AND TABLE 6.4.1.1 NFPA 58. |
| | |
| | 5) P-1: BASED ON GALLON SIZES OF THE TANKS PROVIDE |
| | CLEARANCE DISTANCES FOR THE TANK RELIEF VALVES TO THE |
| | REAR DOOR OPENING, MECHANICAL AIR INTAKES, AND EXTERIOR |
| | SOURCES OF IGNITION- SECTIONS 6.4.4.3 & 6.4.4.4 AND |
| | TABLE 6.4.4.3 NFPA 58. |
| | |
| | 6) P-1 & P-2: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1 |
| | NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE |
| | REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A |
| | 2 PSI REGULATOR IS REQUIRED FOR THE 11 IN.WC SYSTEM. |
| | PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | REGULATOR. |
| | 7) P-1: REFER TO SECTION 6.10.1.7 NFPA 58 AND INDICATE |
| | THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE RELIEF |
| | VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL AIR |
| | INTAKES, AND ANY SOURCE OF IGNITION. |
| | |
| | 8) P-1 & P-2: SUBMIT MANUFACTURER'S DATA SHEETS FOR THE |
| | COOKING APPLIANCES SHOWING APPLIANCE LISTINGS, BTU |
| | CAPACITIES, AND INPUT PRESSURES- SECTION 623.1 FBC FG. |
| | |
| | 9) P-1 & P-2: INDICATE HOW COMBUSTION AIR WILL BE |
| | PROVIDED TO THE COOKING APPLIANCES AND PROVIDED |
| | CALCULATIONS- SECTION 304.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |