Plan Review Notes
Plan Review Notes For Permit 21030333
Permit Number 21030333
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-30 17:00:00WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030333
 ADD: 1700 45TH ST. UNIT: 1801
 CONT: STANISLAUS ENTERPRISE INC.
 TEL: 561-676-6107
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 30TH/ 2021
 ACTION: DENIED
  
 SHEET A-00 THE COVERSHEET STATES THE SCOPE OF WORK TO
 PROVIDE A TAKEOUT/ DINING RESTAURANT:
  
 1A) THE CODE RESEARCH STATES THE PLANS WERE DEVELOPED
 UNDER THE 2017 FBC-B. PLEASE BE AWARE ON DEC. 31ST/
 2020 THE 7TH EDITION, 2020 FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE. PLEASE CORRECT ALL REFERENCES TO THE
 2017 FBC-BUILDING.
  
 1B) (1)THE OCCUPANCY TYPE IS DECLARED A A-2 ASSEMBLY.
 PLEASE REVIEW THE 2020 FBC-BUILDING SECTION 301.2.
 SMALL ASSEMBLY SPACES WHERE (1) THE OCCUPANT LOAD FOR
 ROOMS OR SPACES USED FOR ASSEMBLY PURPOSES HAS A
 OCCUPANT LOAD OF LESS THAN 50 OCCUPANTS AND ASSEMBLY
 USE ROOM WHERE THE ASSEMBLY ROOM IS LES THAN 750 SQ.
 FT. THEN THE OCCUPANCY TYPE IS DECLARED A BUSINESS
 OCCUPANCY.
  
 1B)(2) THE OCCUPANT LOAD IS DECLARED IN THE DINING AREA
 297/15= 20 OCCUPANTS, BUT ON THE S-1 LIFE SAFETY SHEET
 THE SEATING IS SHOWN WITH 24 SEATS. AS THE DESIGNER YOU
 CAN DECLARE AN INCREASED OCCUPANT LOAD SEE SECTION
 1004.2 OF THE 2020 FBC-B PLEASE UPDATE THE PLAN ( SHEET
 A-00 OCCUPANT LOADS) WITH THE INCREASED SEATING LOAD.
  
 1C) THE CODE RESEARCH LIST THIS AS A LEVEL II
 ALTERATION. IN RESEARCHING THE LAST KNOWN USE FOR THIS
 TENANT SPACE (BUSINESS TAX RECORDS) THIS WAS AN
 MERCANTILE OCCUPANCY SELLING CELL PHONES & ACCESSORIES.
 THIS PERMIT THEN IS THEN DECLARED A
 CHANGE OF OCCUPANCY AND SECTION 1001.2.2.1 PARTIAL
 CHANGE OF OCCUPANCY OF THE 2020 FBC-EXISTING BUILDING
 CODE. SECTION 1012 SHALL APPLY IN THE EXISTING BUILDING
 CODE.
  
 1D) PLEASE PROVIDE A SITE PLAN WHERE THIS TENANT SPACE
 IS LOCATED SINCE IN THIS SHOPPING CENTER PART OF IT
 LIES IN THE TOWN OF MANGONIA PARK. THIS MAY NOT BE IN
 THE CITY LIMITS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. GOGGLE MAPS.
  
 2) WIND ANALYSIS CAN NOT BE DETERMINED UNTIL A SITE
 PLAN IS PROVIDED SHOWING THE LOCATION OF THIS TENANT
 SPACE. 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
 GOOGLE MAPS.
  
 3) SHEET S-1 THE LIFE SAFETY SHEET SHOWING 24 SEATS AND
 ONLY ONE ACCESSIBLE SEAT. 24 X0.05= 1.2 ALWAYS ROUND UP
 OR 2 ACCESSIBLE SEATS REQUIRED. 2020FBC-ACCESSIBILITY
 CODE SECTION 226.1 WHERE DINING SURFACES ARE PROVIDED
 FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST 5
 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 4) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS.
 CODE SECTION 902.2 CLEAR FLOOR OR GROUND SPACE FOR
 ACCESSIBLE SEATING. A CLEAR FLOOR SPACE COMPLYING WITH
 305 POSITIONED FOR A FORWARD APPROACH SHALL BE
 PROVIDED. KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
  
 5) SHEET S-1 THE LIFE SAFETY SHEET. 2020 FBC-ACCESS.
 CODE SECTION 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 6) SHEET S-1 THE LIFE SAFETY SHEET. THE FLOOR PLAN
 SHOWS ANEW DRIVE UP WINDOW FOR PICK UP & PAY. THE PLAN
 SHOW A DETAIL 5/ A-04. PLEASE NOTE THERE IS NO A-04
 SHEET WITH DETAILS. 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 6A) SUBMIT PRODUCT APPROVALS FOR COMPLIANCE WITH
 COMPONENTS AND CLADDING. 2020 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOFTOP CURBS FOR
 RTU UNITS AND INTAKE OR EXHAUST FANS (HOODS)
 (G) ROOFTOP PRE-ENGINEERED A/C STANDS
  
 6B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 7) MISSING WIND DESIGN DATA. PRESSURES ARE NEEDED TO BE
 IN VASD FOR ZONES 1.2.3.4 & 5.
 2020 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 7.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 8) MECHANICAL SHEET M-2 MOUNTING , REFERS TO
 MANUFACTURER MOUNTING DRAWINGS WIND LOAD CALCULATIONS,
 AND PLACEMENT OF BRACKETS AND FASTENERS FOR THE RTU TO
 ROOF TOP CURB.
 2020 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM
 FOR ALL ROOF TOP EQUIPMENT, CURBS, FANS OR A/C STANDS,
 AND OR VENTS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE.
  
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 9) SHEET S-1 THE LIFE SAFETY SHEET. AT THE FOOD PICK UP
 WINDOW THERE IS ALSO A NOTE FOR A PREFABRICATED
 OVERHEAD AWNING BY OTHERS SEE ATTACHED SPECS.
  
 10) THE M-2 SHEET SHOWS CURB TO ROOF JOIST ATTACHMENT
 DETAIL PLEASE SHOW COMPLIANCE WITH WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 11) 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION
 OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
  
  
 12) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  