| Plan Review Notes For Permit 21030330 |
| Permit Number |
21030330 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-16 10:16:36 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | | THAT IT BE CONVERTED TO PROJECTDOX | | | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R7 COVERS MULTIPLE ROOF SYSTEM NO. W-1 | | | THRU W-5. PLEASE SELECT CORRECT OPTIONS FOR SYSTEM NO | | | W-2; EXPOSURE (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT | | | (H<15); ULTIMATE WIND SPEED (180). ALL APPLICABLE | | | DETAILS AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON | | | THE PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS | | | NOT SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED | | | SITE-SPECIFIC ENGINEERING | | | |
|