2022-03-02 10:09:08OFFICE/WAREHOUSE RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 5TH REVIEW - PLANS REVISED
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) BUILDING CONSTRUCTION TYPE IS SHOWN AS TYPE II -
 PLEASE SHOW THE WALL AND FLOOR FRAMING MEMBERS TO BE
 NON COMBUSTIBLE PER FBC 602.2 TYPES I AND II.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1.2.NONBEARING EXTERIOR WALLS WHERE
 FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED.
  
 2) PLEASE SHOW THE GRAB BAR BACKING DETAILS AND
 LOCATION FOR THE TOILET AND SHOWER.
  
 FBC 604.5 (1) .GRAB BARS SHALL NOT BE REQUIRED TO BE
 INSTALLED IN A TOILET ROOM FOR A SINGLE OCCUPANT
 ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT FOR
 COMMON USE OR PUBLIC USE PROVIDED THAT REINFORCEMENT
 HAS BEEN INSTALLED IN WALLS AND LOCATED SO AS TO PERMIT
 THE INSTALLATION OF GRAB BARS COMPLYING WITH 604.5.
  
 FBC 608.3 (1).GRAB BARS SHALL NOT BE REQUIRED TO BE
 INSTALLED IN A SHOWER LOCATED IN A BATHING FACILITY FOR
 A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE
 OFFICE, AND NOT FOR COMMON USE OR PUBLIC USE PROVIDED
 THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS AND
 LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB BARS
 COMPLYING WITH 608.3.
  
 3) DRAWING 5/12 - GUARD RAILS AND HANDRAILS REQUIRE
 DIFFERENT HEIGHTS - PLEASE SHOW HANDRAIL HEIGHT TO
 COMPLY WITH FBC 1014.2 HEIGHT.
 HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR
 FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT
 LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38
 INCHES (965 MM). HANDRAIL HEIGHT OF ALTERNATING TREAD
 DEVICES AND SHIPS LADDERS, MEASURED ABOVE TREAD
 NOSINGS, SHALL BE UNIFORM, NOT LESS THAN 30 INCHES (762
 MM) AND NOT MORE THAN 34 INCHES (864 MM).
  
  
  
  
  
  
  
  
  
  
  