Plan Review Notes
Plan Review Notes For Permit 21030310
Permit Number 21030310
Review Stop B
Sequence Number 4
Notes
Date Text
2022-02-01 10:41:41OFFICE/WAREHOUSE RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 4TH REVIEW - PLANS REVISED
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) BUILDING CONSTRUCTION TYPE IS SHOWN AS TYPE II -
 PLEASE SHOW THE WALL AND FLOOR FRAMING MEMBERS TO BE
 NON COMBUSTIBLE PER FBC 602.2
  
 2) PLEASE SHOW THE GRAB BAR BACKING DETAILS AND
 LOCATION FOR THE TOILET AND SHOWER.
  
 FBC 604.5 (1) .GRAB BARS SHALL NOT BE REQUIRED TO BE
 INSTALLED IN A TOILET ROOM FOR A SINGLE OCCUPANT
 ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT FOR
 COMMON USE OR PUBLIC USE PROVIDED THAT REINFORCEMENT
 HAS BEEN INSTALLED IN WALLS AND LOCATED SO AS TO PERMIT
 THE INSTALLATION OF GRAB BARS COMPLYING WITH 604.5.
  
 FBC 608.3 (1).GRAB BARS SHALL NOT BE REQUIRED TO BE
 INSTALLED IN A SHOWER LOCATED IN A BATHING FACILITY FOR
 A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE
 OFFICE, AND NOT FOR COMMON USE OR PUBLIC USE PROVIDED
 THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS AND
 LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB BARS
 COMPLYING WITH 608.3.
  
 3) GUARD RAIL HEIGHT AT STAIRS NEED TO BE A MIN. HEIGHT
 OF 42 INCHES PER FBC 1015.3
  
 4) PLEASE SHOW THE STAIR HAND RAIL EXTENSIONS AT TOP
 AND BOTTOM OF STAIR PER FBC 1014.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
  
  
  
  
  
  
  
  