| 2022-02-01 10:41:41 | OFFICE/WAREHOUSE RENO |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | 4TH REVIEW - PLANS REVISED |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | |
| | 1) BUILDING CONSTRUCTION TYPE IS SHOWN AS TYPE II - |
| | PLEASE SHOW THE WALL AND FLOOR FRAMING MEMBERS TO BE |
| | NON COMBUSTIBLE PER FBC 602.2 |
| | |
| | 2) PLEASE SHOW THE GRAB BAR BACKING DETAILS AND |
| | LOCATION FOR THE TOILET AND SHOWER. |
| | |
| | FBC 604.5 (1) .GRAB BARS SHALL NOT BE REQUIRED TO BE |
| | INSTALLED IN A TOILET ROOM FOR A SINGLE OCCUPANT |
| | ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT FOR |
| | COMMON USE OR PUBLIC USE PROVIDED THAT REINFORCEMENT |
| | HAS BEEN INSTALLED IN WALLS AND LOCATED SO AS TO PERMIT |
| | THE INSTALLATION OF GRAB BARS COMPLYING WITH 604.5. |
| | |
| | FBC 608.3 (1).GRAB BARS SHALL NOT BE REQUIRED TO BE |
| | INSTALLED IN A SHOWER LOCATED IN A BATHING FACILITY FOR |
| | A SINGLE OCCUPANT ACCESSED ONLY THROUGH A PRIVATE |
| | OFFICE, AND NOT FOR COMMON USE OR PUBLIC USE PROVIDED |
| | THAT REINFORCEMENT HAS BEEN INSTALLED IN WALLS AND |
| | LOCATED SO AS TO PERMIT THE INSTALLATION OF GRAB BARS |
| | COMPLYING WITH 608.3. |
| | |
| | 3) GUARD RAIL HEIGHT AT STAIRS NEED TO BE A MIN. HEIGHT |
| | OF 42 INCHES PER FBC 1015.3 |
| | |
| | 4) PLEASE SHOW THE STAIR HAND RAIL EXTENSIONS AT TOP |
| | AND BOTTOM OF STAIR PER FBC 1014.6 HANDRAIL EXTENSIONS. |
| | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |