| 2021-12-03 10:47:43 | 11/03/21 3RD PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET P0.1, UNDER APPLICABLE CODES, IT REFERS TO |
| | THE P, 6 THE EDITION. PLEASE PROVIDE THE YEAR, |
| | PLUMBING, AND ACCESSIBILITY REFERENCED PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 101.4 REFERENCED CODES. |
| | |
| | 2. FOR THE SECOND-FLOOR RESTROOM, PLEASE PROVIDE |
| | DOCUMENTATION THE SECOND-FLOOR DOES NOT REQUIRE |
| | VERTICAL ACCESSIBILITY, AND IT HAS LESS THAN FIVE |
| | OCCUPANTS, AND SUCH ROOMS ARE NOT OPEN TO THE PUBLIC |
| | PER THE 2020 FBC SEC. 201.1.1. |
| | |
| | 3. DONE |
| | |
| | 4. DONE |
| | |
| | 5. ON SHEET A1.01, IT SHOWS AN ADA SINK DETAIL BUT NO |
| | CLEAR FLOOR SPACE IN FRONT OF THE SINK. PLEASE SHOW AND |
| | PROVIDE DIMENSIONS PER THE 2020 FBC ACC SEC. 606.3. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |