Plan Review Notes
Plan Review Notes For Permit 21030310
Permit Number 21030310
Review Stop B
Sequence Number 3
Notes
Date Text
2021-11-24 10:13:38OFFICE/WAREHOUSE RENO
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 3RD REVIEW - PLANS REVISED
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC
 602.1
  
 2) PLEASE SHOW THE "STORAGE" AREA OCCUPANCY
 CLASSIFICATION PER FBC CHAPTER 3. (S1 ORS2)
  
 3) PLEASE SHOW THE ADDED REST ROOM TO COMPLY WITH FBC
 ACCESSIBILITY PER FBC ACCESSIBILITY ADVISORY 206.2.3
 MULTI-STORY BUILDINGS AND FACILITIES. SPACES AND
 ELEMENTS LOCATED ON A LEVEL NOT REQUIRED TO BE SERVED
 BY AN ACCESSIBLE ROUTE MUST FULLY COMPLY WITH THIS
 CODE. FBC A213.1 GENERAL. WHERE TOILET FACILITIES AND
 BATHING FACILITIES ARE PROVIDED, THEY SHALL COMPLY WITH
 213.
  
 4) PLEASE SHOW THE EGRESS PATH DIMENSION TO THE EXIT
 FROM THE MOST REMOTE CORNER OF THE 2ND FLOOR STORAGE
 FBC 1017.3
  
 5) PLEASE SHOW THE ADDED STAIR - CONNECTIONS, RISER
 HEIGHT, TREAD DEPTH PER FBC 1011.5
  
 6) PLEASE SHOW THE STAIR GUARD AND HAND RAIL DETAILS
 (HEIGHT, ATTACHMENTS, TOP AND BOTTOM EXTENSIONS ETC,) -
 FBC 1011.11
  
 7) PLEASE SHOW THE 2ND FLOOR GUARD RAIL DETAILS
 (ATTACHMENTS, HEIGHT, OPENING LIMITATIONS ETC,) - FBC
 1015.1
  
 8) PLEASE SHOW RESTROOM WALL, FLOOR AND BASEBOARD
 FINISHES TO COMPLY WITH FBC 1210 (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 9) PLEASE SHOW THE ACCESSIBLE PATH (VERTICAL
 ACCESSIBILITY) TO THE 2ND FLOOR PER FBC 201.1.1 FOR AN
 EXEMPTION THE 2ND FLOOR STORAGE AREA WILL NEED TO BE
 LABELED "STORAGE SPACE NOT DESIGNED FOR HUMAN
 OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK
 AREAS".
  
 10) PLEASE REVISE THE FLOOR PLAN (3 OF 12) TO SHOW THE
 BEARING WALLS.
  