| Plan Review Notes For Permit 21030310 |
| Permit Number |
21030310 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-10-25 09:21:47 | NEW UPLOADED DRAWINGS TO SIGNATURE FILE CONTAIN (12) | | | DRAWINGS. THERE ARE (18) DRAWINGS SUBMITTED ORIGINALLY. | | | IT APPEARS AS THOUGH (6) DRAWINGS ARE MISSING. IN | | | ADDITION ONLY (1) DRAWING,( LABELED ELECTRICAL | | | LIGHTING) IN THE SIGNATURE FILE, CONTAINS A DIGITAL | | | SIGNATURE AND THIS SIGNATURE APPEARS TO BE INVALID. | | | PLEASE CORRECT AS DESCRIBED BELOW | | | | | | PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN | | | (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE | | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | | DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE | | | WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE | | | CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET | | | MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL | | | TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481 | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | |
|