| Notes |
| Date |
Text |
| 2021-06-07 09:37:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 0.00 - WITHIN THE INDEX OF DRAWINGS THERE | | | ARE INDICATIONS OF FP SHHEETS; HOWEVER, THERE ARE NO FP | | | SHEETS ATTACHED. | | | | | | PLEASE ATTACHED THOSE SHEETS | | | | | | 1A) ANY WORK ON THE FIRE PROTECTION SYSTEM(S), | | | INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMIT(S) | | | AND SHOP DRAWINGS. | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPICABLE NOTE | | | OF ACKNOWLEDGEMENT. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|