| Plan Review Notes For Permit 21030310 |
| Permit Number |
21030310 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-07 09:11:40 | OFFICE/WAREHOUSE RENO | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) BUILDING CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE | | | REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN | | | EFFECT (FBC 2020) | | | 2) PLEASE SHOW THE "STORAGE" AREA OCCUPANCY | | | CLASSIFICATION PER FBC CHAPTER 3. | | | 3) PLEASE SHOW THE ADDED REST ROOM TO COMPLY WITH FBC | | | ACCESSIBILITY PER FBC ACCESSIBILITY ADVISORY 206.2.3 | | | MULTI-STORY BUILDINGS AND FACILITIES. SPACES AND | | | ELEMENTS LOCATED ON A LEVEL NOT REQUIRED TO BE SERVED | | | BY AN ACCESSIBLE ROUTE MUST FULLY COMPLY WITH THIS | | | CODE. FBC A213.1 GENERAL. WHERE TOILET FACILITIES AND | | | BATHING FACILITIES ARE PROVIDED, THEY SHALL COMPLY WITH | | | 213. | | | 4) PLEASE SHOW CEILING HEIGHTS TO COMPLY WITH FBC | | | 1208.2 | | | 5) PLEASE SHOW RESTROOM WALL, FLOOR AND BASEBOARD | | | FINISHES TO COMPLY WITH FBC 1210 (DRYWALL IS NOT | | | CONSIDERED A HARD SURFACE) | | | |
|