| Plan Review Notes For Permit 21030277 |
| Permit Number |
21030277 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-12 15:37:05 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PRODUCT APPROVAL ROOFING SYSTEM CHOSEN HAS A MAXIMUM | | | DESIGN PRESSURE OF (-97.5) - WIND ZONE 3 FOR EXPOSURE | | | "C" REQUIRES A PRESSURE OF (-108.17) 2020 FBC TABLE | | | R301.2(2) - PLEASE PROVIDE ADDITIONAL ATTACHMENT | | | DETAILS FROM A QUALIFIED DESIGN PROFESSIONAL PER NOTE | | | NUMBER 9 ON THE PRODUCT APPROVAL. | | | |
|