| 2021-11-23 10:37:19 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21030271 |
| | 11/23/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENT #2 FROM THE 1ST |
| | REVIEW PRINTED BELOW HAS NOT BEEN COMPLETELY RESOLVED. |
| | PLEASE PROVIDE ITEMS 2- A,B,D,F,G,H,I,J |
| | |
| | 2) THE GAS RISER SHALL BE A COMPLETE GAS RISER FOR THE |
| | RESIDENCE THAT INCLUDES ALL NEW AND EXISTING GAS PIPING |
| | AND APPLIANCES AND EQUIPMENT- SECTIONS 401.3 & 401.4 |
| | FBC FG. PLEASE PROVIDE: |
| | B) DELIVERY PRESSURE AT THE METER. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | F) TYPES AND SIZES OF PIPING. |
| | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| | UNIONS. |
| | H) OUTLET PRESSURES AT REGULATORS. |
| | I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | J) PIPE SIZING TABLE USED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |