| 2021-03-23 16:18:46 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21030263 360 S ROSEMARY AVE # 1400 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.DRAWING A0.01 LIFE SAFETY IS MISSING FROM PROJECT |
| | DOCS. PER WPB FBC 107.2.1, PROVIDE. |
| | 2.PER WPB FBC 107.2.1, SHOW CLEAR FLOOR SPACES FOR |
| | ACCESSIBLE SINKS SHOWING COMPLIANCE WITH FBC ACC |
| | SECTION 305. |
| | 3.PER WPB FBC 107.2.1, PROVIDE A WATER RISER DIAGRAM. |
| | SHOW ALL VALVES, REQUIRED WATER HAMMER ARRESTORS, |
| | FILTERS AND REQUIRED BACKFLOW PREVENTORS. PROVIDE A |
| | SCHEDULE FOR WATER HAMMER ARRESTORS, FILTERS AND |
| | BACKFLOW PREVENTORS. NOTE BACKFLOW PREVENTORS SHALL BE |
| | SPECIFIED AND MODEL NUMBERS SHALL REFLECT LEAD |
| | CONSTRUCTION. PROVIDE VALVED OUTLET WITH BACKFLOW |
| | PREVENTOR FOR COFFEE MAKER. PROVIDE BACKFLOW PREVENTOR |
| | FOR ICE MACHINE. REGARDING BACKFLOW PREVENTORS, REFER |
| | TO FBC PL 608. |
| | 4.REFERENCE PLAN SHEET P1.01: NON PRESSURE PIPING PLAN |
| | (SANITARY); PER FBC PL 802.4, READY ACCESS SHALL BE |
| | PROVIDED TO WASTE RECEPTORS (FLOOR SINK). SEE FBC PL |
| | CHAPTER 2, DEFINITIONS; READY ACCESS. THAT WHICH |
| | ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO BE |
| | DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR |
| | MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND |
| | WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR |
| | SIMILAR DEVICE. PER WPB FBC 107.2.1, CONFIRM THAT FLOOR |
| | SINK IS READILY ACCESSIBLE. |
| | 5.REFERENCE PLAN SHEET P2.01: APPLICABLE CODES AND |
| | STANDARDS. PER WPB FBC 107.2.1 REPLACE 2017 WITH 2020 |
| | TO REFLECT THE CURRENT EDITION OF THE FLORIDA BUILDING, |
| | PLUMBING AND MECHANICAL CODES. |
| | |
| | PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, |
| | PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S |
| | SPECIFICATION AND INSTALLATION GUIDE FOR THE NEW ICE |
| | MACHINE FURNISHED BY OTHERS. DOCUMENT SHALL BE |
| | SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL |
| | INSPECTION. MACHINE SHALL BE INSTALLED IN COMPLIANCE |
| | WITH ALL REQUIREMENTS OF FBC PL PRIOR TO FINAL |
| | INSPECTION (SEE WPB FBC 111.1). PROCEED AT YOUR OWN |
| | RISK. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-243-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |