Plan Review Notes
Plan Review Notes For Permit 21030263
Permit Number 21030263
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-23 16:18:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21030263 360 S ROSEMARY AVE # 1400
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.DRAWING A0.01 LIFE SAFETY IS MISSING FROM PROJECT
 DOCS. PER WPB FBC 107.2.1, PROVIDE.
 2.PER WPB FBC 107.2.1, SHOW CLEAR FLOOR SPACES FOR
 ACCESSIBLE SINKS SHOWING COMPLIANCE WITH FBC ACC
 SECTION 305.
 3.PER WPB FBC 107.2.1, PROVIDE A WATER RISER DIAGRAM.
 SHOW ALL VALVES, REQUIRED WATER HAMMER ARRESTORS,
 FILTERS AND REQUIRED BACKFLOW PREVENTORS. PROVIDE A
 SCHEDULE FOR WATER HAMMER ARRESTORS, FILTERS AND
 BACKFLOW PREVENTORS. NOTE BACKFLOW PREVENTORS SHALL BE
 SPECIFIED AND MODEL NUMBERS SHALL REFLECT LEAD
 CONSTRUCTION. PROVIDE VALVED OUTLET WITH BACKFLOW
 PREVENTOR FOR COFFEE MAKER. PROVIDE BACKFLOW PREVENTOR
 FOR ICE MACHINE. REGARDING BACKFLOW PREVENTORS, REFER
 TO FBC PL 608.
 4.REFERENCE PLAN SHEET P1.01: NON PRESSURE PIPING PLAN
 (SANITARY); PER FBC PL 802.4, READY ACCESS SHALL BE
 PROVIDED TO WASTE RECEPTORS (FLOOR SINK). SEE FBC PL
 CHAPTER 2, DEFINITIONS; READY ACCESS. THAT WHICH
 ENABLES A FIXTURE, APPLIANCE OR EQUIPMENT TO BE
 DIRECTLY REACHED WITHOUT REQUIRING THE REMOVAL OR
 MOVEMENT OF ANY PANEL, DOOR OR SIMILAR OBSTRUCTION AND
 WITHOUT THE USE OF A PORTABLE LADDER, STEP STOOL OR
 SIMILAR DEVICE. PER WPB FBC 107.2.1, CONFIRM THAT FLOOR
 SINK IS READILY ACCESSIBLE.
 5.REFERENCE PLAN SHEET P2.01: APPLICABLE CODES AND
 STANDARDS. PER WPB FBC 107.2.1 REPLACE 2017 WITH 2020
 TO REFLECT THE CURRENT EDITION OF THE FLORIDA BUILDING,
 PLUMBING AND MECHANICAL CODES.
  
 PROVISO: PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 PROVIDE AS A DEFERRED SUBMITTAL MANUFACTURER?S
 SPECIFICATION AND INSTALLATION GUIDE FOR THE NEW ICE
 MACHINE FURNISHED BY OTHERS. DOCUMENT SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. MACHINE SHALL BE INSTALLED IN COMPLIANCE
 WITH ALL REQUIREMENTS OF FBC PL PRIOR TO FINAL
 INSPECTION (SEE WPB FBC 111.1). PROCEED AT YOUR OWN
 RISK.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS