| 2021-03-10 13:49:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) IT APPEARS THAT THESE WALLS HAVE ALREADY BEEN |
| | INSTALLED AND ARE EXISTING. THIS BUILDING ALSO HAS FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | THE NEW WALLS REQUIRE A REVIEW OF THE EXISTING FIRE |
| | SPRINKLER HEAD LOCATION FOR CODE COMPLIANT PROTECTION |
| | BY A FIRE SPRINKLER CONTRACTOR. |
| | |
| | ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A LETTER OF REVIEW AND |
| | COMPLIANCE FROM A FIRE SPRINKLER CONTRACTOR OR PROVIDE |
| | A NOTE OF ACKNOWLEDGEMENT THAT A SEPARATE PERMIT WILL |
| | BE SUBMITTED WITH SHOP DRAWINGS FOR THE FIRE SPRINKLER |
| | MODIFICATIONS. |
| | |
| | |
| | |
| | 2) THIS BUILDING ALSO HAS A FIRE ALARM SYSTEM. |
| | |
| | THE NEW WALLS REQUIRE A REVIEW OF THE EXISTING FIRE |
| | ALARM DEVICES FOR CODE COMPLIANT PROTECTION BY A FIRE |
| | ALARM CONTRACTOR. |
| | |
| | ANY WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER |
| | SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A LETTER OF REVIEW AND |
| | COMPLIANCE FROM A FIRE ALARM CONTRACTOR OR PROVIDE A |
| | NOTE OF ACKNOWLEDGEMENT THAT A SEPARATE PERMIT WILL BE |
| | SUBMITTED WITH SHOP DRAWINGS FOR THE FIRE ALARM |
| | MODIFICATIONS. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |