2021-06-12 13:15:132ND REVIEW FBC-2020 PLUMBING
 PERMIT-21030214
 6/12/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020 FBC EX- FLORIDA EXISTING BUILDING CODE
 SEVENTH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1- 2ND REQUEST: 4) A CATHODIC PROTECTION SYSTEM SHALL
 BE REQUIRED PER NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) AND
 SHALL BE MONITORED PER NFPA 58 SEC.6.6.6.1 (J). SUBMIT
 DETAILS ON THE TYPE OF CATHODIC PROTECTION, SIZE (LBS)
 & NUMBER OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE
 CABLE. NFPA 58 SEC. 6.17.3.
 2- DOCCUMENT SUBMITTED FROM TIE DOWN MANUFACTURING
 SHALL BE STAMPED BY THE ENGINEER
 3- PERMIT APPLICATION STATES DUAL FUEL NATURAL GAS AND
 PROPANE. GENERATOR MANUFACTURE ONLY STATES NATURAL GAS-
 PLEASE CLARIFY HOW NATURAL GAS AND PROPANE WILL BE
 INTERCONNECTED TO THE GENERATOR.
 4- INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020
 FBC FUEL GAS RES. SEC. G2413.2.
 5- SUBMIT A COPY OF THE SIZING TABLE USED IN THE DESIGN
 FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF
 PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2020 FBC FUEL GAS SEC. 402.3 OR 2020 FBC FUEL
 GAS RES. SEC. G2413.3
 6- SUBMIT GENERATOR MANUFACTURES FULL INSTALLATION
 MANUAL AND SPECIFICATIONS . FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  