2021-03-11 15:51:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE WIND DESIGN DATA REFERENCES THE 2017 FBC
 RESIDENTIAL AND ASCE 7 - 10. BASED ON THE PERMIT
 APPLICATION DATE OF 3/4/2021, THIS PROJECT IS UNDER THE
 2020 FBC BUILDING SEVENTH EDITION AND ASCE 7-16 . THE
 FBC BUILDING APPLIES AND NOT THE FBC RESIDENTIAL. THE
 PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH EDITION
 (2017). THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT
 ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION. FS CHAPTER 553
  
 2) THE GENERATOR PAD IS SPECIFIED AS 4" THICK CONCRETE.
 BASED ON THE GENERATOR SPECIFICATIONS IT WEIGHS OVER
 4,000 LBS. WITH THE ACOUSTIC ENCLOSURE. OTHER
 GENERATORS OF SIMILAR SIZE HAVE 6" OR 8" THICK SLABS.
 SUBMIT CALCULATIONS TO SHOW THAT A 4" SLAB IS ADEQUATE.
 FBC AMENDMENTS 107.2.1.2
  
 3) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA, ZONE "AE" WITH A BASE FLOOD ELEVATION OF 12.2'
 NAVD 88. THE CITY HAS A REQUIRED FREEBOARD OF 2 FEET
 MORE. THIS MAKES THE REQUIRED ELEVATION 14.2' NAVD. THE
 GENERATOR WILL NEED TO BE ELEVATED ABOVE 14.2' NAVD OR
 BE DRY FLOOD PROOFED. SHOW HOW THIS WILL BE
 ACCOMPLISHED. A PRE-CONSTRUCTION ELEVATION CERTIFICATE
 WILL BE REQUIRED BEFORE THE PERMIT IS ISSUED. A FINAL
 ELEVATION CERTIFICATE WILL BE REQUIRED AT THE FINAL
 INSPECTION. FBC 1612
  
 4) SUBMIT A SITE PLAN WITH THE ELEVATIONS DEFINED IN
 NAVD 88. FBC 107.2.1
  