Notes
Date Text
2021-03-09 10:18:5703/09/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. A HEATED SWIMMING POOL SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS
 PER THE 2017 FBC- ENERGY- SEC. R 403.10.3.
  
 2. THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM
 FLOW DO NOT SHOW ALL FRICTION LOSS THROUGH ALL
 COMPONENTS, AND THE HEATER IS MISSING ON THE HAYWARD
 CALCULATOR CHART. PLEASE CORRECT PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE
 WILL BE REQUIRED AT THE WATER METER BY A LICENSED
 CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE
 CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS
 DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A
 BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE
 REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW
 CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B.
 AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE
 INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS.
 THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT.
  
 4. PLEASE PROVIDE THE TYPE OF BACKFLOW ON HOSE BIBB IN
 THE AUTOFILL DETAIL, I.E., PVB PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  