| Date |
Text |
| 2021-03-19 15:15:36 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | PERMIT 21030196 |
| | |
| | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: |
| | |
| | 1) SHEET T-02 (RISER DIAGRAM): WHERE UNGROUNDED |
| | CONDUCTORS ARE INCREASED IN SIZE FROM THE MINIMUM SIZE |
| | THAT HAS SUFFICIENT AMPACITY FOR THE INTENDED |
| | INSTALLATION, EQUIPMENT GROUNDING CONDUCTORS SHALL BE |
| | INCREASED IN SIZE PROPORTIONALLY, ACCORDING TO THE |
| | CIRCULAR MIL AREA OF THE UNGROUNDED CONDUCTORS. NEC |
| | 250.122(B) |
| | |
| | - FEEDER FROM WIREWAY #1 TO 75 KVA TRANSFORMER |
| | (DISTANCE 534 FT): GROUNDING EQUIPMENT CONDUCTOR MUST |
| | BE #4 CU MINIMUM (INCREASE FACTOR = 1.6) |
| | - FEEDER FROM WIREWAY #1 TO 30 KVA TRANSFORMER |
| | (DISTANCE 586 FT): GROUNDING EQUIPMENT CONDUCTOR MUST |
| | BE AT LEAST #4 CU (INCREASE FACTOR = 3.2) |
| | |
| | 2) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CURRENTS AT |
| | EACH OF THE WIREWAYS. FBC 107 |
| | |
| | 3) SHEET T-02 GENERAL ELECTRICAL NOTE #7: INDICATES ALL |
| | CONDUCTORS SHALL BE CU BUT RISER DIAGRAM SPECIFIES AL |
| | CONDUCTORS FOR FEEDERS. I ASSUME NOTE IS REFERRING TO |
| | BRANCH CIRCUITS FROM PANELS. PLEASE MODIFY NOTE TO |
| | CLARIFY. FBC 107 |
| | |
| | 4) VALUE OF WORK ON PERMIT SEEM LOW. PLEASE PROVIDE A |
| | SIGNED CONTRACT WITH THE WORK VALUE. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| | MS |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | DEVELOPMENT SERVICES |
| | CITY OF WEST PAM BEACH |
| | 401 CLEMATIS STREET, 1ST FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | |
| | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS |
| | |
| | PHONE: 561-805-6746. |
| | EMAIL: [email protected] |
| | |