Plan Review Notes
Plan Review Notes For Permit 21030193
Permit Number 21030193
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-01 14:32:2904/01/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-0, UNDER CODES, YOU ONLY REFERENCE
 BUILDING CODE 202, WHICH IS ONLY ONE VOLUME. PLEASE
 INCLUDE THE PLUMBING COMMERCIAL AND ACCESIBILTIES CODES
 PER THE WPB AMENDMENTS TO THE FBC SEC. 102.3
 APPLICATION OF REFERENCES.
  
 2. ON SHEET A-1;
 A. IT SHOWS A SINK IN AN OPEN AREA THAT SHALL COMPLY
 WITH THE ACCESSIBILITY CODE. PLEASE SHOW THE CLEAR
 FLOOR SPACE AND DIMENSION PLUS PROVIDE CABINET DETAIL
 SHOWING THE SINK AND OR LAVS HEIGHT OF 34" INCHES
 MAXIMUM PER THE 2017 FBC ACC SEC. 606.3.
  
 B. THE TOILET IS OF THE WALL SAYS 1"- 4", AND THERE IS
 A RANGE TO 1'- 6" PLEASE ADD IT PER THE 2020 FBC ACC.
 SEC. 604.2 LOCATION.
  
 C. ON THE DIMENSION OF THE HORIZONTAL GRAB BARS, PLEASE
 SHOW THE CENTERLINE PER THE 2020 FBC ACC. 604.5.1 SIDE
 WALL AND 604.5.2 REAR.
  
 D. ON THE REAR WALL, PLEASE SHOW THE REAR GRAB BAR 12"
 FROM THE CENTER OF THE TOILET PER THE 2020 FBC ACC.
 SEC. 604.5.2.
  
 E. PLEASE REMOVE OR STRIKE THROUGH THE WATER COOLER
 DETAIL THAT DOES NOT PERTAIN TO THIS SET OF PLANS FOR
 THIS STRUCTURE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. PLEASE SHOW THE WATER CLOSET FLUSH CONTROL LOCATION
 ON THE OPEN SIDE ON THE FIRST DETAIL IN THE TYPE TOILER
 ROOM ELEVATION PER THE 2017 FBC SEC. 604.6 FLUSH
 CONTROLS.
  
 G. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 3. ON SHEET A-3;
  
 A. IT SHOWS ON SIDE ELEVATION THE TOILET PAPER
 DISPENSER AT 36? FROM THE REAR WALL. PLEASE SHOW TOILET
 PAPER DISPENSERS 7" INCHES MINIMUM AND 9" INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE DISPENSER PER THE 2020 FBC ACC SEC. 604.7.
  
 4. ON SHEET P-2;
  
 A. IN GENERAL, PLUMBING NOTES NUMBER 18 REFERS TO 2014.
 PLEASE CORRECT TO CURRENT CODE PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. THE KITCHEN AND THE MOP SINK CANNOT DISCHARGE INTO
 THE BATHROOM GROUP'S WET VET; IT MUST BE DOWNSTREAM PER
 THE 2017 FBC SECTION R3108.1 HORIZONTAL WET VENT
 PERMITTED.
  
 C. IN YOUR FLOW RATE CONSUMPTION, IT REFERS TO P
 2903.2A. THIS IS NOT A REFERENCE CODE. PLEASE CLARIFY
 AND REMOIVE DISHWASHER AHD WASHING MACHINE THAT IS NOT
 ON THIS STRUCTURE PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2017 FBC BUILDING SEC. 1210.2.2 AND 2017 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 5. ON SHEET, LS-1 SHOWS THE MOP SINK IN A DIFFERENT
 LOCATION. PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  