| Plan Review Notes For Permit 21030193 |
| Permit Number |
21030193 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-30 15:05:07 | RESTROOM REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) RESTROOM BASE BOARD NEEDS TO COMPLY WITH FBC | | | 1210.2.1 FLOORS AND WALL BASES. | | | IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND | | | SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH | | | FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, | | | NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE | | | WALLS NOT LESS THAN 4 INCHES (102 MM). | | | | | | 2) WALLS IN RESTROOM AND MOP SINK NEED TO COMPLY WITH | | | FBC 1210.2.2 WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) | | | | | | 3) PLEASE SHOW THE TOILET REAR GRAB BAR LOCATION | | | DIMENSIONS (FROM CENTER OF THE TOILET LOCATION) TO | | | COMPLY WITH FBC ACCESSIBILITY FIGURE 604.5.2 |
|