| Plan Review Notes For Permit 21030170 |
| Permit Number |
21030170 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-11 14:32:01 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) REVISE THE NOTE ON THE SURVEY. THE GENERATOR EXHAUST | | | IS REQUIRED TO BE 10 FEET FROM ANY OPENINGS TO A | | | BUILDING. FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 2) SUBMIT A MIAMI-DADE OF FLORIDA PRODUCT APPROVAL OR | | | SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE | | | PRE-FABRICATED GENERATOR PAD. THE SIZE DIMENSIONS AND | | | WEIGHT OF THE GENERATOR MUST MATCH THE ONES ON THE | | | ENGINEERING OR PRODUCT APPROVAL. THE GENERATOR PAD | | | DRAWINGS THAT WERE SUBMITTED DO NOT MATCH THE GENERATOR | | | SPECIFICATIONS FOR SIZE AND WEIGHT. FBC AMENDMENTS | | | 107.2.1 | | | |
|