| 2021-03-18 11:43:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21030167 216 ASHWORTH ST |
| | MP #21010248 |
| | |
| | GENERAL NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE |
| | EMERGENCY GENERATOR |
| | |
| | 1ST REVIEW |
| | |
| | GAS COMMENTS: DENIED |
| | |
| | 1. SPECIFICATION SHEET FOR GAS RANGE IS COMPLETELY |
| | INADEQUATE. PER WPB FBC 107.2.1, PROVIDE FULL |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | GAS RANGE SHOWING THE TOTAL 65,000 BTUS NOTED ON THE |
| | RISER DIAGRAM. |
| | |
| | 2. PER WPB FBC 107.2.1, INDICATE ON THE SPECIFICATION |
| | SHEETS FOR ALL EQUIPMENT THE APPLICABLE MODEL NUMBER |
| | FOR EACH PIECE OF EQUIPMENT. ALSO, THE BBQ GRILL |
| | APPEARS TO BE 42,000 BTUS NOT 40,000. |
| | |
| | 3. PER WPB FBC 107.2.1, INDICATE ON THE, MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL PROVIDED, THE |
| | FOLLOWING FOR THE NAVIEN TANKLESS WATER HEATER: |
| | A) THE MANUFACTURER?S MODEL NUMBER |
| | B) THE TYPE OF VENT BEING USED (IE. DIRECT VENT-INDOOR, |
| | INDIRECT VENT-INDOOR). IF INDIRECT VENT, PROVIDE |
| | COMBUSTION AIR CALCULATIONS PER FBC FG SEC.304.1 AND |
| | SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT AND ANCHORING DETAILS OF THE GAS |
| | VENT(S) PER FBC FG SECTIONS 502 THRU 505 OR FBC RES |
| | SECTIONS G2426 THROUGH G2439. ESPECIALLY SEE FBC FG |
| | SECTION 503.8(3), TABLE 503.8 WITH NOTE REFERRING TO |
| | SECTION 503.8(2) AS IS APPLICABLE TO BTU INPUT RATING |
| | IN EXCESS OF 150,000 BTUS. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION/INSTALLATION MANUAL FOR THE DRYER. |
| | |
| | 5. PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR FOR THE GAS APPLIANCES LOCATED INSIDE |
| | THE BUILDING PER FBC FG SEC.304.1, 614.6 (CLOTHES |
| | DRYERS) OR FBC RES SEC. G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). |
| | |
| | 6. PER WPB FBC 107.2.1, SUBMIT A HOUSE PLAN AND IF |
| | APPLICABLE A SURVEY PLAN SHOWING THE LOCATION OF THE |
| | GAS METER AND ALL GAS APPLIANCES, INDOORS AND OUTDOORS. |
| | SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO ANY VENT TERMINALS AND OUTDOOR |
| | APPLIANCES. PLEASE NOTE EXHAUST VENTS AND THE GENERATOR |
| | (WHICH REQUIRES A SEPARATE PERMIT) SHALL BE INSTALLED A |
| | MINIMUM OF 10' FROM MECHANICAL OR GRAVITY AIR INTAKES |
| | (WINDOW AND DOOR OPENINGS) INTO THE BUILDING PER FBC |
| | RES R303.5.1. ADDITIONALLY, THE EMERGENCY GENERATOR |
| | SHALL BE LOCATED A MINIMUM OF 5' AWAY FROM COMBUSTIBLE |
| | WALLS PER NFPA 37 SEC. 4.1.4. THE HOUSE PLAN CAN BE |
| | HAND DRAWN BUT AS THERE IS AN ARCHITECTURAL PLAN AND |
| | SURVEY IN THE MASTER, IT IS RECOMMENDED THAT THE |
| | INFORMATION IS PROVIDED BY THE ARCHITECT AND APPLICABLE |
| | SHEETS ARE PROVIDED TO YOU FOR YOUR PERMIT APPLICATION. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 7. PER FBC FG 404.17.3, PROVIDE MINIMUM 18 AWG YELLOW |
| | INSULATED COPPER TRACER WIRE SUITABLE FOR DIRECT BURIAL |
| | OR OTHER APPROVED CONDUCTOR ADJACENT TO UNDERGROUND |
| | NONMETALLIC PIPING. ACCESS SHALL BE PROVIDED TO THE |
| | TRACER WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE |
| | GROUND AT EACH END OF THE NONMETALLIC PIPING. THE |
| | TRACER WIRE SIZE SHALL BE NOT LESS THAN 18 AWG AND THE |
| | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| | |
| | 8. PER WPB FBC 107.2.1, SHOW TRANSITION FITTINGS AT |
| | CONNECTIONS MADE BETWEEN METALLIC AND PLASTIC PIPING |
| | CONFORMING TO ASTM D2513 CATEGORY I OR ASTM F1973 |
| | COMPLYING WITH FBC FG 404.17.2. |
| | |
| | 9. PER WPB FBC 107.2.1, SHOW THE MAXIMUM DISTANCE FROM |
| | THE MP REGULATOR(S) TO THE APPLIANCE(S) BEING SERVED, |
| | TO SHOW COMPLIANCE WITH FBC FG 402.4.1. |
| | END OF COMMENTS. |
| | |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE GAS COMMENTS FROM THE |
| | FIRST REVIEW. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | SUBMITTED PLAN WAS HAND DRAWN BY THE CONTRACTOR |
| | (QUALIFIER) AND SIGNED IN ACCORDANCE WITH WPB FBC |
| | 107.3.4.3, SCANNED AND UPLOADED TO PROJECT DOCS FOR |
| | THIS REVIEW. PLEASE NOTE THAT WHEN SCANNED DRAWINGS ARE |
| | SUBMITTED WITH CONTRACTOR'S PRINTED NAME, SIGNATURE AND |
| | LICENSE NUMBER IN ACCORDANCE WITH WPB FBC 107.3.4.3, A |
| | PAPER PLAN WITH WET SIGNATURE SHALL BE PROVIDED TO THE |
| | BUILDING DEPARTMENT FOR HARD RECORD FILE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-243-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21030167 216 ASHWORTH ST |