| 2021-05-27 05:57:54 | |
| | 1) POOL HEATER SPECS HAVE BEEN SUBMITTED WHICH HAVE |
| | BEEN HIGHLIGHTED TO SHOW A 399,000 BTU UNIT. PLEASE ADD |
| | THE BRANCH LINE TO THE HEATER ON THE RISER DRAWING, |
| | SIZE THE LINE AND SHOW THE LOCATION ON THE FLOOR PLAN- |
| | SECTION G2413.2 FBC RES.2ND REQUEST. |
| | |
| | 2) PLACE A NOTE ON THE FLOOR PLAN TO INDICATE THE |
| | GENERATOR WILL BE UNDER A SEPARATE PERMIT AND WILL BE |
| | INSTALLED A MINIMUM OF 10 FT. FROM OPENINGS INTO THE |
| | BUILDING- SEE LOCATION OF DOOR IN RELATION TO THE |
| | GENERATOR.SECTION R303.5 FBC RES.3RD REQUEST. |
| | |
| | 3) THE BTU LOAD OF THE POOL HEATER MUST BE ADDED TO THE |
| | TOTAL BTU LOAD OF THE SYSTEM WHICH WILL BE A TOTAL BTU |
| | LOAD OF 1,019,700 BTU'S.THIS MEANS THE 3/4 PE PIPE FROM |
| | THE METER IS UNDERSIZED PER TABLE G2413.4(8) OF |
| | FBC-RES. THE MINIMUM SIZE SHALL BE 1 INCH FROM THE |
| | METER AND POSSIBLY FURTHER DEPENDING ON THE LOCATION OF |
| | THE POOL HEATER. |
| | |
| | 4) PROVIDE THE LENGTH, WIDTH AND HEIGHT DIMENSIONS OF |
| | THE LAUNDRY ROOM. A MINIMUM OF 1000 CUBIC FEET OF |
| | COMBUSTION AIR IS REQUIRED FOR THE DRYER AND THE |
| | SUBMITTED PLAN REVIEW RESPONSE SHEET SHOWS 956 CUBIC |
| | FEET OF COMBUSTION AIR WHICH IS DEFICIENT. COMPLY WITH |
| | FBC-RES. SEC.G2407.5.1.ADDITIONAL COMBUSTION AIR IS |
| | REQUIRED. |
| | |
| | 5) INDICATE ON THE PLAN WHICH SIZING TABLE FROM THE |
| | FUEL GAS CODE IS BEING USED FOR THE LOW PRESSURE SCH. |
| | 40 METALLIC PIPE. THE TABLE REFERENCED ON THE DRAWING |
| | IS FOR A 2 PSI SYSTEM. |
| | |
| | 6) THE PLAN CALLS OUT AN EHD OF 15 FOR THE GAS LIINE TO |
| | THE RANGE. THIS IS EQUIVALENT OF 3/8 INCH PIPING PER |
| | THE REFERENCED SIZING TABLE WHICH IS COMPLIANT.IS IT |
| | THE INTENT TO INSTALL 1/2 INCH PIPE? IF SO, REVISE THE |
| | DRAWING TO SHOW THE CORRECT EHD/PIPE SIZE. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |