| 2021-04-26 14:09:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) NOT COMPLIED. [THE GENERATOR PAD ENGINEERING THAT |
| | WAS SUBMITTED, REFERENCES TO 2017 FBC SIXTH EDITION AND |
| | THSI PERMIT IS UNDER THE 2020 FBC SEVENTH EDITION. THE |
| | PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH EDITION |
| | (2017). THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT |
| | ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR |
| | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND |
| | REFERENCE THE 2020 FBC SEVENTH EDITION. FS CHAPTER 553] |
| | SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD |
| | ANCHORING DETAILS. IF A PREFABRICATED SLAB IS USED, |
| | SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING. |
| | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. FBC AMENDMENTS |
| | 107.2.1 & FBC-R301 |
| | |
| | 2) NOT COMPLIED. [THIS NEEDS TO BE SPECIFIED ON THE |
| | GENERATOR LOCATION SURVEY.] SPECIFY THAT THE GENERATOR |
| | EXHAUST IS TO BE LOCATED AT LEAST 10 FEET FROM OPENINGS |
| | INTO A BUILDING. FBC-R303.5.1 INTAKE OPENINGS. |
| | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS |
| | SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM |
| | ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS, |
| | CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS |
| | AND LOADING DOCKS. |
| | |
| | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |