2021-04-26 14:09:51PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. [THE GENERATOR PAD ENGINEERING THAT
 WAS SUBMITTED, REFERENCES TO 2017 FBC SIXTH EDITION AND
 THSI PERMIT IS UNDER THE 2020 FBC SEVENTH EDITION. THE
 PLANS HAVE SEVERAL REFERENCES TO THE FBC SIXTH EDITION
 (2017). THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT
 ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION. FS CHAPTER 553]
 SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD
 ANCHORING DETAILS. IF A PREFABRICATED SLAB IS USED,
 SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING.
 THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON
 ELECTRONICALLY SUBMITTED DOCUMENTS. FBC AMENDMENTS
 107.2.1 & FBC-R301
  
 2) NOT COMPLIED. [THIS NEEDS TO BE SPECIFIED ON THE
 GENERATOR LOCATION SURVEY.] SPECIFY THAT THE GENERATOR
 EXHAUST IS TO BE LOCATED AT LEAST 10 FEET FROM OPENINGS
 INTO A BUILDING. FBC-R303.5.1 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  