| Plan Review Notes For Permit 21030161 |
| Permit Number |
21030161 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-24 08:01:23 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT GENERATOR PAD DRAWINGS WITH GENERATOR TO PAD | | | ANCHORING DETAILS. IF A PREFABRICATED SLAB IS USED, | | | SUBMIT PRODUCT APPROVALS OR SITE SPECIFIC ENGINEERING. | | | THE ENGINEER'S DIGITAL SIGNATURE IS REQUIRED ON | | | ELECTRONICALLY SUBMITTED DOCUMENTS. FBC AMENDMENTS | | | 107.2.1 & FBC-R301 | | | | | | 2) SPECIFY THAT THE GENERATOR EXHAUST IS TO BE LOCATED | | | AT LEAST 10 FEET FROM OPENINGS INTO A BUILDING. | | | FBC-R303.5.1 INTAKE OPENINGS. MECHANICAL AND GRAVITY | | | OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED NOT LESS | | | THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS | | | CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, | | | STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | |
|