Plan Review Notes
Plan Review Notes For Permit 21030155
Permit Number 21030155
Review Stop B
Sequence Number 1
Notes
Date Text
2021-03-26 11:26:39FLAG POLE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE A SITE PLAN/SURVEY SHOWING THE
 LOCATION OF THE FLAG POLE - WITH DIMENSIONS FROM THE
 BUILDING, PROPERTY LINES ETC..
 2) FLAG POLE IS SUBJECT TO WIND LOADS.FBC 1609 PLEASE
 PROVIDE SIGNED AND SEALED DETAILS SHOWING THE
 FOUNDATION AND POLE ATTACHMENT REQUIREMENTS FROM A
 DESIGN PROFESSIONAL.
 3) PLEASE SHOW THE WIND DESIGN DATA USED FOR DESIGN PER
 FBC 1603.1.4
  