Plan Review Notes
Plan Review Notes For Permit 21030143
Permit Number 21030143
Review Stop P
Sequence Number 3
Notes
Date Text
2021-08-12 17:57:483RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21030143
 8/12/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS 2, 6, & 8
 FROM THE 1ST REVIEW AND 2ND REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES FOR CLARIFICATION. PLEASE CONTACT
 ME IF I CAN BE OF ANY ASSISTANCE IN GETTING THE
 PLUMBING PLANS APPROVED.
  
 2) FAILED. P0.1: PLEASE INCLUDE THE MOP SINK,
 3-COMPARTMENT SINK, PREP SINKS, AND HAND SINKS TO THE
 FIXTURE SCHEDULE- SECTION 107.2.1 WPB. PROVIDE TYPE OF
 WALL FINISH MATERIAL TO BE INSTALLED AROUND THE MOP
 SINK- SECTION 1210.2.2 FBC B. PLEASE IDENTIFY THE
 LOCATION OF THE MOP SINK ON THE PLANS, ADD IT TO THE
 SCHEDULE, AND PROVIDE THE WALL FINISH MATERIAL AS
 PREVIOUSLY REQUESTED.
  
 6) FAILED. P5.1: THE KEY NOTES REFERENCE CIVIL DRAWINGS
 FOR POINTS OF CONNECTIONS AND WATER METER AND BACKFLOW
 PREVENTER LOCATIONS- PLEASE PROVIDE THE PLANS. PLEASE
 NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. PROVIDE
 THE CIVIL DRAWINGS OR REQUEST DEFERRED SUBMITTAL TO BE
 PROVIDED WITH THE GREASE INTERCEPTOR PERMIT.
  
 8) FAILED. P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P. SHEETS
 P2.1 & P5.1: THE ISOMETRIC DRAWING ON P5.1 SHOWS A
 DIRECT WASTE CONNECTION FOR THE 3-COMPARTMENT SINK.
 TYPICALLY, A FLOOR SINK IS PROVIDED HOWEVER THE PIPING
 PLAN ON P2.1 SHOWS A FD. PLEASE CORRECT THE DETAIL ON
 P0.1 TO SHOW EACH WELL OF THE SINK DISCHARGING
 INDEPENDENTLY TO THE WASTE RECEPTOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  