Plan Review Notes
Plan Review Notes For Permit 21030143
Permit Number 21030143
Review Stop G
Sequence Number 3
Notes
Date Text
2021-08-12 17:41:033RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21030143
 8/12/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST AND
 2ND REVIEWS ARE LISTED BELOW AS PASSED OR FAILED. NOTES
 FOR FURTHER CLARIFICATION HAVE BEEN ADDED TO FAILED
 COMMENTS. PLEASE CONTACT ME IF I CAN BE OF ANY
 ASSISTANCE IN GETTING THE FUEL GAS PLANS APPROVED.
  
 1) FAILED. SHEET P5.1: BASED ON THE SIZING TABLE
 402.4(2) LISTED ON THE PLAN, THE 3/4 IN. PIPE AT METER
 IS UNDERSIZED FOR THE 363.000 GAS LOAD AT 32 FT. TDL.
 THE TOTAL CONNECTED LOAD WITH THE WATER HEATER IS
 562,000 BTUS. BASED ON THE LISTED PIPE SIZING TABLE ON
 THE PLAN (402.4(2)) THE 1-INCH MAIN GAS PIPE IS
 UNDERSIZED. PLEASE CLARIFY IF THIS IS A LOW PRESSURE
 SYSTEM PER THE SELECTED PIPE SIZING TABLE OR POSSIBLY A
 2 PSI SYSTEM WHICH WOULD ONLY REQUIRE A MINIMUM ?-INCH
 MAIN PIPE FOR THE TOTAL LOAD AT 32-FT. TDL- SEE TABLE
 402.4(5).
  
 2) PASSED. P5.1: SHOW THE LOCATION OF AUTO GAS VALVE-
 SECTION 10.4.1 NFPA 96.
  
 3) FAILED P5.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE COOKING APPLIANCES - SECTION 304.1 FBC FG. THE NEW
 CALCULATIONS ARE USING THE EQUATION FOUND IN SECTION
 304.5.2 FBC FG WHICH CAN ONLY BE USED WHEN THERE IS A
 KNOWN AIR INFILTRATION RATE LESS THAN .40 AIR CHANGES
 PER HOUR (ACH). THE CALCULATIONS PROVIDED ARE USING AN
 ACH OF 17.6. THE CALCULATION IS ALSO USING 2535 CFMS OF
 O/A AS THE BASIS OF THE ACH, HOWEVER THE AIR IS BEING
 SUPPLIED MECHANICALLY AS OPPOSED TO INFILTRATION. IF
 USING MECHANICAL AIR PLEASE REFER TO SECTION 304.9 AND
 PROVIDE THE CALCULATION. PLEASE REVIEW SECTION 304.5.1
 BELOW:
 THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT
 THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE
 LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION
 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL
 BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL
 APPLIANCES LOCATED WITHIN THE SPACE. ROOMS
 COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE
 APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED
 WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE
 CONSIDERED TO BE PART OF THE REQUIRED VOLUME.
  
 4) PASSED- DEFERRED SUBMITTAL. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE COOKING APPLIANCES AND THE WATER
 HEATER- SECTIONS 623.1 & 624.1 FBC FG.
  
 5) PASSED- DEFERRED SUBMITTAL. P0.1: PROVIDE THE
 MANUFACTURER OF THE GAS WATER HEATER IN THE FIXTURE
 SCHEDULE- SECTION 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  
  