Plan Review Notes
Plan Review Notes For Permit 21030143
Permit Number 21030143
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-03 09:07:292ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21030143
 6/3/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW LISTED BELOW STILL EXIST. NO CORRECTED OR
 NARRATIVE RESPONSES WERE SUBMITTED.
  
 1) SHEETS P0.1, P2.1, P5.1 PROVIDE THE FOLLOWING GREASE
 INTERCEPTOR INFO AND DETAILS: SIZING CALCULATIONS,
 EQUIPMENT SCHEDULE, ENLARGED PIPING DETAIL THAT SHOWS
 THE LOCATION AND TYPE OF SAMPLING PORT, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR ALL COMPONENTS-
 SECTIONS 1003.3.5 & 1003.3.7 FBC P.
  
 2) P0.1: PLEASE INCLUDE THE MOP SINK, 3-COMPARTMENT
 SINK, PREP SINKS, AND HAND SINKS TO THE FIXTURE
 SCHEDULE- SECTION 107.2.1 WPB. PROVIDE TYPE OF WALL
 FINSH MATERIAL TO BE INSTALLED AROUND THE MOP SINK-
 SECTION 1210.2.2 FBC B.
  
 3) P2.1 & P5.1: PLEASE RELOCATE THE DRAINAGE FROM THE
 HAND SINKS FROM THE GREASE WASTE TO THE SANITARY
 SYSTEM- SECTION 1003.3.1 FBC P. PLEASE NOTE THE CHIEF
 PLUMBING INSPECTOR FOR THE CITY OF WPB HAS RESTRICTED
 HAND SINKS FROM DRAINING INTO THE GREASE WASTE SYSTEM
 BASED ON HIS INTERPRETATION OF THE CODE. PLEASE NOTE
 THAT THE FIXTURES AT THE OUTDOOR BAR MAY ALSO BE
 PROHIBITED- SEE COMMENT #5 NOTES.
  
 4) LS.1.1 & P SHEETS: SHOW THE LOCATION OF THE REQUIRED
 DRINKING FOUNTAINS AND PROVIDE THE PLUMBING PIPING
 DETAILS. IF THE INTENTION IS TO PROVIDE DRINKING WATER
 FREE OF CHARGE, PLEASE PLACE A NOTE ON THE PLAN- TABLE
 403.1 AND SECTION 410.4 FBC P.
  
 5) P2.1, P3.1 & P5.1: PROVIDE THE FIXTURE, APPLIANCE,
 AND EQUIPMENT SCHEDULE THAT CORRELATES WITH THE
 NUMBERED OUTLETS IN THE DRAWINGS- SECTION 107.2.1 WPB.
 A COMPLETE PLUMBING REVIEW CANNOT BE ACCOMPLISHED WITH
 THE SCHEDULE.
  
 6) P5.1: THE KEY NOTES REFERENCE CIVIL DRAWINGS FOR
 POINTS OF CONNECTIONS AND WATER METER AND BACKFLOW
 PREVENTER LOCATIONS- PLEASE PROVIDE THE PLANS. PLEASE
 NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR SHALL
 OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 8) P0.1: PROVIDE AN INDIRECT WASTE DETAIL FOR THE
 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  