| 2021-06-03 09:20:34 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21030143 |
| | 6/3/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW LISTED BELOW STILL EXIST. NO CORRECTED PLANS OR |
| | NARRATIVE RESPONSES WERE SUBMITTED. |
| | |
| | 1) SHEET P5.1: BASED ON THE SIZING TABLE 402.4(2) |
| | LISTED ON THE PLAN, THE 3/4 IN. PIPE AT METER IS |
| | UNDERSIZED FOR THE 363.000 GAS LOAD AT 32 FT. TDL. |
| | |
| | 2) P5.1: SHOW THE LOCATION OF AUTO GAS VALVE- SECTION |
| | 10.4.1 NFPA 96. |
| | |
| | 3) P5.1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | COOKING APPLIANCES - SECTION 304.1 FBC FG. |
| | |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCES AND THE WATER HEATER- SECTIONS 623.1 & 624.1 |
| | FBC FG. |
| | |
| | 5) P0.1: PROVIDE THE MANUFACTURER OF THE GAS WATER |
| | HEATER IN THE FIXTURE SCHEDULE- SECTION 624.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |