| Plan Review Notes For Permit 21030143 |
| Permit Number |
21030143 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-06-17 09:07:00 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 2ND BUILDING REVIEW DENIED; THE FOLLOWING ITEMS FROM | | | THE LAST REVIEW LIST STILL NEED TO BE ADDRESSED: | | | | | | 3) FBC B 107.2, PLEASE SUBMIT ALL PRODUCT APPROVALS. | | | EACH PRODUCT APPROVAL NEEDS TO BE REVIEW STAMPED. | | | | | | 11) FBC B 107.2, PLEASE PROVIDE THE ATTACHMENT DETAILS | | | FOR THE ROOF TOP EQUIPMENT TO THE EXISTING ROOF OR | | | PRODUCT APPROVALS SHOWING COMPLIANCE WITH WINDLOADS PER | | | FBC B 1609. | | | | | | 12) FBC B 1015.6, PLEASE PROVIDE ROOF TOP GUARD RAIL | | | REQUIREMENTS AT INDICATORS SHOWN ON SHEET A2.0.1. |
|