Plan Review Notes
Plan Review Notes For Permit 21030143
Permit Number 21030143
Review Stop M
Sequence Number 1
Notes
Date Text
2021-04-08 07:49:111ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21030143
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ATTACH NOTE ON THE DRAWINGS STATING THAT THE
 KITCHEN HOOD, GREASE DUCT AND MAKEUP AIR WILL BE
 SUBMITTED AS A SEPARATE PERMIT AND PLAN REVIEW.
  
 2) PLEASE ATTACH A NOTE ON THE DRAWINGS STATING THAT
 THE REFRIGERATION EQUIPMENT WILL BE SUBMITTED AS A
 SEPARATE PERMIT AND PLAN REVIEW.
  
 3) THE OUTDOOR AIR CALCULATION FOR THE INDOOR DINING
 APPEARS TO BE LOW ACTUAL CFM SHOULD BE 384. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 4) THE OUTDOOR AIR CALCULATIONS SHOULD ALSO SHOW THE
 OUTDOOR AIR REQUIRED FOR THE KITCHEN. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
 5) SHEET M6.1 (ROOF TOP A/C EQUIPMENT SCHEDULE) OUTDOOR
 AIR CFM IS UNDERSIZED.
  
 6) PLEASE SHOW THAT GUARDS ARE INSTALLED FOR THE
 MAINTENANCE OF THE UNITS THAT ARE WITHIN 10 FT. OF ROOF
 EDGE. FBC M 304.11
  
 7) PLEASE SHOULD THE ROOF ACCESS FOR SERVICE OF THE
 UNITS ON THE ROOF. FBC M 306.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  