| 2021-04-08 07:49:11 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21030143 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE ATTACH NOTE ON THE DRAWINGS STATING THAT THE |
| | KITCHEN HOOD, GREASE DUCT AND MAKEUP AIR WILL BE |
| | SUBMITTED AS A SEPARATE PERMIT AND PLAN REVIEW. |
| | |
| | 2) PLEASE ATTACH A NOTE ON THE DRAWINGS STATING THAT |
| | THE REFRIGERATION EQUIPMENT WILL BE SUBMITTED AS A |
| | SEPARATE PERMIT AND PLAN REVIEW. |
| | |
| | 3) THE OUTDOOR AIR CALCULATION FOR THE INDOOR DINING |
| | APPEARS TO BE LOW ACTUAL CFM SHOULD BE 384. FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 4) THE OUTDOOR AIR CALCULATIONS SHOULD ALSO SHOW THE |
| | OUTDOOR AIR REQUIRED FOR THE KITCHEN. FBC M 403.3.1.1 |
| | AND TABLE 403.3.1.1 |
| | |
| | 5) SHEET M6.1 (ROOF TOP A/C EQUIPMENT SCHEDULE) OUTDOOR |
| | AIR CFM IS UNDERSIZED. |
| | |
| | 6) PLEASE SHOW THAT GUARDS ARE INSTALLED FOR THE |
| | MAINTENANCE OF THE UNITS THAT ARE WITHIN 10 FT. OF ROOF |
| | EDGE. FBC M 304.11 |
| | |
| | 7) PLEASE SHOULD THE ROOF ACCESS FOR SERVICE OF THE |
| | UNITS ON THE ROOF. FBC M 306.5 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |