Plan Review Notes
Plan Review Notes For Permit 21030143
Permit Number 21030143
Review Stop E
Sequence Number 1
Notes
Date Text
2021-04-05 15:30:43ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) FAULT CURRENT CALCULATION AND LABELS FOR SERVICE
 MISSING FROM PLANS 110.9, 110.10, 110.24
  
 2) GFI PROTECTION MISSING FROM KITCHEN, AND WITHIN 6'
 OF SINKS 210.8(B)