| Plan Review Notes For Permit 21030143 |
| Permit Number |
21030143 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-04-05 15:30:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FAULT CURRENT CALCULATION AND LABELS FOR SERVICE | | | MISSING FROM PLANS 110.9, 110.10, 110.24 | | | | | | 2) GFI PROTECTION MISSING FROM KITCHEN, AND WITHIN 6' | | | OF SINKS 210.8(B) |
|