2021-04-07 16:14:20COMMERCIAL ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THAT THE PARKING LOT RESTRIPING WILL BE
 ON A SEPARATE PERMIT.
 2) PLEASE SHOW THAT THE SITEWALL WILL BE ON A SEPARATE
 PERMIT.
 3) PLEASE PROVIDE A COMPLETE MIAMI DADE OR FLORIDA
 STATE PRODUCT APPROVAL FOR THE EXTERIOR DOORS, WINDOWS
 AND ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 4) DRAWING LS.1.1 SHOWS THE EGRESS GATE WIDTH AT 4' -
 DRAWING A 7.0.1 SHOWS ON THE DOOR SCHEDULE THE EGRESS
 GATE TO BE 4'4" - PLEASE CLARIFY - THE MAXIMUM WIDTH
 SHOULD BE 4' PER FBC 1010.1.1
 5) THE AWNING AREA SHOULD HAVE EMERGENCY LIGHTING PER
 FBC 1008.3.2 (4).
 6) PLEASE SHOW THE KNEE AND TOE CLEARANCES AT THE
 ACCESSIBLE BAR AREA AND THE RESTROOM ACCESSIBLE SINKS
 PER FBC A306
 7) PLEASE SHOW THE ACCESSIBLE BAR AREA AT EACH BAR PER
 FBC A226.1
 8) PLEASE SHOW THE BUILDING SQUARE FOOTAGE.
 9) PLEASE SHOW THE AREA SQUARE FOOTAGE UNDER THE CANOPY
 - FBC 3105.3.2 AREA.NO FABRIC AWNING OR FABRIC-COVERED
 FRAME SHALL EXCEED THE AREA OF THE BUILDING TO WHICH IT
 IS ATTACHED.
 10) PLEASE SHOW ROOF TOP MECHANICAL EQUIPMENT CURB
 HEIGHT OR STAND CLEARANCE FROM THE ROOFING TO COMPLY
 WITH FBC 1510.10.
 11) PLEASE PROVIDE ATTACHMENT DETAILS FOR THE ROOF TOP
 MECHANICAL EQUIPMENT TO THE EXISTING ROOF OR PRODUCT
 APPROVALS TO COMPLY WITH THE WIND LOADS FBC 1609
 12) PLEASE SHOW THE REQUIRED GUARD RAILS ON THE ROOF
 PER FBC 1015.6 MECHANICAL EQUIPMENT, SYSTEMS AND
 DEVICES.
 GUARDS SHALL BE PROVIDED WHERE VARIOUS COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND
 EACH END OF SUCH COMPONENTS. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
  