Plan Review Notes
Plan Review Notes For Permit 21030139
Permit Number 21030139
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-17 11:17:10WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21030139
 ADD: 901 45TH ST. ST. MARY?S / REPLACEMENT OF MRI
 EQUIPMENT.
 CONT: WESTBROOKE CORP.
 TEL: 561-395-4126
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: MONDAY, MAY 17TH/ 2021
 ACTION: DENIED
  
 1) 2ND REQUEST/ SEMI-COMPLIED. A NEW GENERIC CUT
 SECTION OF A ROOF TOP CURB IS SHOWN. THE DETAIL DOES
 NOT INDICATE THE TYPE OF ROOF DECK. IF CONCRETE OR IF
 THIS ROOF DECK IS COMPOSED OF A BAR JOIST SYSTEM AND
 METAL B DECKING, SPACING OF BAR JOIST, POINT LOADING OF
 THE BAR JOIST, IF NEW METAL ANGLE IRON IS NEEDED TO
 FORM THE SUPPORT FRAMING FOR THE NEW ROOF TOP RTU. THE
 DETAIL ALSO FAILS TO PROVIDE THE PROPOSED ANCHORING
 SYSTEM OF THE RTU UNIT TO THE CURB, NO CALCULATIONS
 WERE SUBMITTED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED, SEE 1ST ROUND OF COMMENTS.
  
 1ST ROUND OF COMMENTS. SHEET A2.1 NOTE # 7STATES NEW
 ROOF CURB & MECHANICAL VENT (OUTSIDE AIR INTAKE FAN).
 SEE MECHANICAL PLANS. SHEET M1.0 DETAIL FOR NEW ROOF
 CURB AND LOW PROFILE OUTSIDE AIR INTAKE FAN. THERE ARE
 NO DETAILS IN EITHER THE ARCHITECTURAL OR MECHANICAL
 PLANS FOR THE ROOF FRAMING AROUND THE NEW ROOF TOP
 OPENING. HOW THE ROOF TOP CURB AND FAN ARE GOING TO BE
 ANCHORED TO THE MWFRS (MAIN WIND FORCE RESISTING
 SYSTEM).
  
 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 1A)(1) 2ND REQUEST. THE NEW DETAIL ON SHEET A8.1 DETAIL
 16 DOES NOT STATE THE TYPE OF ROOF DECK.
 1ST ROUND OF COMMENTS. THE STEEL ROOF FRAMING MEMBERS
 AND ROOF DECK PANELS WILL NEED TO BE EITHER BOLTED OR
 WELDED ON HE JOBSITE FOR INSTALLATION. WELDED OR BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT
 TIME OF FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 1A)(2) NEW COMMENT. SHEET A8.1 DIRECTLY BELOW THE NEW
 DETAIL 16 THERE IS A DETAIL # 15 AND WITHIN THE NOTE IT
 STATES THE CONTRACTOR TO VERIFY THAT HARDWARE USED IN
 THE MRI PROCEDURE ROOM DOES NOT CONTAIN FERROUS METALS,
 DOES THIS ALSO INCLUDE THE AREA DIRECTLY ABOVE THE
 ENCLOSED ROOM, FOR EXAMPLE IF THERE IS BAR JOIST OR IF
 A CONCRETE DECK RE-BAR IN THE DECK ITSELF AND OR THE
 ROOF TOP CURB AND RTU? 107.2.1.2 ADDITIONAL INFORMATION
 NEEDED.
  
 1B) SEMI-COMPLIED. NO PRODUCT INFORMATION WAS SUPPLIED
 FOR THE ROOF TOP CURB. 2020 FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(D) ROOFING PRODUCTS AND ASSEMBLIES,
 ROOF TOP CURBS & ROOF TOP VENTILATORS,
  
 1C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 2) SEMI-COMPLIED. THIS REVIEW CYCLE THERE IS NO WIND
 DESIGN CRITERIA PROVIDED. 2020 FBC-B 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM
 OF THE STRUCTURE:
  
 2.1.COMPLIED. ULTIMATE DESIGN WIND SPEED, VULT,
 (3-SECOND GUST), MILES PER HOUR AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2.2. 2ND REQUEST. THE EXPOSURE GIVEN IS AN B EXPOSURE.
 ST. MARY?S IS LOCATED ON THE TOP OF A HILL AND THE ONLY
 LARGE STRUCTURE AROUND, WE BELIEVE THIS IS AN C
 EXPOSURE, OR SURFACE ROUGHNESS C. OPEN TERRAIN WITH
 SCATTERED OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS
 THAN 30 FEET IN HEIGHT.
 RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 2.4. COMPLIED. APPLICABLE INTERNAL PRESSURE
 COEFFICIENT.
 2.5. 2ND REQUEST. NO PRESSURES WERE GIVEN FOR THE ROOF
 TOP OR THE EQUIPMENT TO BE LOCATED ON THE ROOF TOP.
 DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
 2.6. 2ND REQUEST. TABLE 1609.7(2) ADJUSTMENT FACTORS
 FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR
 THE BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND
 SPEED CONVERSION VULT TO VASD.
  
 3) 2ND REQUEST. ANY INFORMATION BEING SENT TO THE
 BUILDING DEPARTMENT NEEDS TO FOLLOW STATE STATUTES IN
 REGARDS TO ARCHITECTURAL REVIEW. A SHOP DRAWING STAMP
 OF REVIEW AND APPROVAL. THE 24-PAGE SIGNA ARTIST IPM
 FINAL STUDY IS NOT SIGNED NOR SEALED BY AN ENGINEER OR
 SHOP DRAWING STAMP OF APPROVAL BY THE DESIGNER OF
 RECORD. FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  