Plan Review Notes
Plan Review Notes For Permit 21030139
Permit Number 21030139
Review Stop P
Sequence Number 1
Notes
Date Text
2021-04-06 13:48:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. RE: A8.1/DETAIL 1AND 3; COUNTERTOP IS NOTED TO BE
 MAXIMUM 2 FEET 10 INCHES (34 INCHES) VERTICAL DISTANCE
 FROM FINISH FLOOR TO TOP. PER WPB FBC 107.2.1, PROVIDE
 NOTE AT DETAILS STATING ?LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 606.3.?
  
 2. RE: A1.1; PER WPB FBC 107.2.1, PROVIDE ON PLAN,
 CLEAR FLOOR SPACE AND APPROACH FOR NEW ACCESSIBLE SINK
 AS REQUIRED BY FBC ACC 305.3 AND 804.3.1.
  
 3. RE: P1.1, NOTE 2; PER WPB FBC 107.2.1, PROVIDE
 PIPING SPECIFICATIONS FOR DOMESTIC WATER (PIPE VALVES,
 FITTINGS). NOTE ALL COMPONENTS SHALL BE LEAD FREE TO
 COMPLY WITH FBC PL 605.2.
 PROVIDE SPECIFICATION FOR HOT WATER INSULATION AS MAY
 BE REQUIRED PER FBC PL E607.5.
  
 4. RE: P1.1, NOTE 3; PER WPB FBC 107.2.1, PROVIDE A
 SLAB REPAIR DETAIL. SHOW THE WIDTH OF THE REPAIR, THE
 MINIMUM THICKNESS OF THE CONCRETE TO BE REPLACED, AND
 THE PSI OF THE CONCRETE. SHOW THE SIZE AND LENGTH OF
 THE DOWELS, THE MINIMUM EMBEDMENT DEPTH INTO THE
 EXISTING SLAB, THE ANCHORING MATERIAL FOR THE DOWELS
 AND THE SPACING OF THE DOWELS ON CENTER. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AND
 THE REQUIRED VAPOR BARRIER OVER WELL-COMPACTED SOIL. A
 COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE FOR A
 FINAL INSPECTION.
  
 5. RE: P1.1, NOTE 3 AND 4; PER WPB FBC 107.2.1, PROVIDE
 PIPING SPECIFICATIONS FOR SANITARY WASTE AND VENT
 PIPING.
  
 6. RE: P1.1, NOTE 5 AND 6; PER WPB FBC 107.2.1, SPECIFY
 TYPE AND THICKNESS OF INSULATION REQUIRED FOR
 CONDENSATE DRAINS.
  
 7. RE: P1.1, NOTE 5; PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE CONDENSATE DISCHARGE TO THE EXISTING
 DRYWELL.
  
 8. RE: P1.1, NOTE 6; PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE CONDENSATE DISCHARGE TO THE EXISTING
 FLOOR DRAIN. PROVIDE PROTECTION TO ELIMINATE ANY
 TRIPPING HAZARD THAT MIGHT OCCUR DUE TO THIS
 INSTALLATION.
  
 9. PER WPB FBC 107.2.1, PROVIDE HANGER DETAIL FOR
 HORIZONTAL PIPING INCLUDING BUT NOT LIMITED TO HANGER
 TYPE, ROD TYPE, SHIELDS AND STRUCTURAL ATTACHMENTS.
 PROVIDE SCHEDULE FOR ROD SIZE. REFERENCE FBC PL 308.5
 FOR SPACING.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21030139 901 45TH ST
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved