| 2021-03-22 15:07:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21030139 |
| | ADD: 901 45TH ST. ST. MARY?S / REPLACEMENT OF MRI |
| | EQUIPMENT. |
| | CONT: WESTBROOKE CORP. |
| | TEL: 561-395-4126 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY, MARCH 22ND/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A2.1 NOTE # 7STATES NEW ROOF CURB & MECHANICAL |
| | VENT (OUTSIDE AIR INTAKE FAN). SEE MECHANICAL PLANS. |
| | SHEET M1.0 DETAIL FOR NEW ROOF CURB AND LOW PROFILE |
| | OUTSIDE AIR INTAKE FAN. THERE ARE NO DETAILS IN EITHER |
| | THE ARCHITECTURAL OR MECHANICAL PLANS FOR THE ROOF |
| | FRAMING AROUND THE NEW ROOF TOP OPENING. HOW THE ROOF |
| | TOP CURB AND FAN ARE GOING TO BE ANCHORED TO THE MWFRS |
| | (MAIN WIND FORCE RESISTING SYSTEM). |
| | |
| | 2020 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | 1A) THE STEEL ROOF FRAMING MEMBERS AND ROOF DECK PANELS |
| | WILL NEED TO BE EITHER BOLTED OR WELDED ON HE JOBSITE |
| | FOR INSTALLATION. WELDED OR BOLTED CONNECTIONS. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2020 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT 561-805-6666. |
| | 1B) 2020 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: (31)(D) ROOFING |
| | PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS & ROOF TOP |
| | VENTILATORS |
| | 1C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| | DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| | PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC. |
| | 2) THIS REVIEW CYCLE THERE IS NO WIND DESIGN CRITERIA |
| | PROVIDED. 2020 FBC-B 1603.1.4 WIND DESIGN DATA. THE |
| | FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL BE |
| | SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | 2.2. RISK CATEGORY. |
| | 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| | 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING.. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | 3) THE 24-PAGE SIGNA ARTIST IPM FINAL STUDY IS NOT |
| | SIGNED NOR SEALED BY AN ENGINEER OR SHOP DRAWING STAMP |
| | OF APPROVAL BY THE DESIGNER OF RECORD. FL 61G1-23.015 |
| | (2) THE ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND |
| | REVIEWING ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |