Plan Review Notes
Plan Review Notes For Permit 21030129
Permit Number 21030129
Review Stop E
Sequence Number 1
Notes
Date Text
2021-03-05 13:10:30ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SHOW WHAT TYPE AND SIZE OF CIRCUIT TO TUB
 215.5
  
 2) ADDITIONAL SMOKE ALARMS SHALL BE REQUIRED PER FBC
 R314.
 PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER
 CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 R314.3, FBC 107.2.1