Plan Review Notes
Plan Review Notes For Permit 21030085
Permit Number 21030085
Review Stop B
Sequence Number 2
Notes
Date Text
2021-05-03 13:40:27WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21030085
 W. P. B. PERMIT: 20070536
 ADD: 7185 DEER POINT LN.
 CONT: COASTAL GREEN ENERGY SOLUTIONS
 TEL: 813-512-6014
 E-MAIL: COASTALGREENSOLUTIONSENERGY.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MAY 03RD / 2021
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE NOTE THIS COMMENT SHOULD HAVE
 BEEN CAUGHT ON THE ORIGINAL PERMIT REQUIRING THE
 CONTRACTOR TAKING OWNERSHIP OF ALL DOCUMENTS DESIGNED/
 CREATED BY HIS FIRM AND BEING SUBMITTED TO THE BUILDING
 DEPARTMENT. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS WILL NEED TO IDENTIFY THEMSELVES
 AS THE AUTHOR OF THE PLANS. PLEASE PRINT YOUR NAME
 (QUALIFIER) , SIGN YOUR NAME AND LICENSE NUMBER FOR THE
 TRADE YOU ARE LICENSED IN AND PLANS DRAWN, SCHEDULES ,
 ETC.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
  
 2)SEMI-COMPLIED. THIS RESIDENCE WAS BUILT BACK IN 1996
 AND DIDN?T REQUIRE LARGE MISSILE WINDOWS OR STORM
 SHUTTERS. UNDER THE 2020 EXISTING BUILDING CODE SECTION
 707.4 EXCEPTION 1 REQUIRES EITHER STORM SHUTTERS OR
 LARGE MISSILE IMPACT GLAZING. PLEASE PROVIDE A FLOOR
 PLAN AND OPENING SIZES FOR ALL GLAZED WINDOWS AND DOORS
 AND PER-CENTAGE OF OPENINGS BEING REPLACED IN A
 12-MONTH PERIOD.
  
 3) NEW COMMENT 5/03/2021. SUBMITTED THIS REVIEW, A
 PRODUCT APPROVAL, FL 14110-R5 SHUTTERS- FABRIC STORM
 PANELS.
 FL BLD CODE 2017 SECTION 107.2.5.,1609.1.2, 1715.8 &
 EXIST BUILD CODE 706.4 PROCEDURES: A COMPLETE
 INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING
 SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, SPACING OF ANCHORS, TYPE OF ANCHORS, AND
 ASSOCIATED PRESSURES, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, IF
 APPLICABLE, ETC.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  