| Plan Review Notes For Permit 21030031 |
| Permit Number |
21030031 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-05-07 10:08:13 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 1&2 FAMILY - SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1 CITY POLICY REQUIRES A SEPERATE PERMIT FOR EACH | | | STRUCTURE HAVING A SEPERATE ADDRESS. SUBMIT A PERMIT | | | APPLICATION FOR THE REAR STRUCTURE. PERMITS WILL TRAVEL | | | TOGETHER WITH ALL PLANS AND DOC'S REMAININGUNDER PERMIT | | | 21030031. INSPECTIONS SHALL BE SCHEDULED FOR EACH | | | PERMIT. | | | E-MAIL YOUR APPLIOCATION TO [email protected] | | | YOU MAY INDICATE ON THE APPLICATION THAT THE VALUE IS | | | INCLUDED UNDER PERMIT 21030031. WORK DESCRIPTION SHALL | | | BE "REAR STRUCTURE - SHUTTERS 9 THRU 17". | | | |
|