| 2021-05-18 16:04:04 | RESIDENTIAL(R3) ELEVATION CERTIFICATE. SECOND BUILDING |
| | REVIEW COMMENTS |
| | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| | SUBMITTAL #21030009 (MASTER 16061174). |
| | |
| | COMMENTS FOR REVISED ELEVATION CERTIFICATE CERTIFIED ON |
| | 05/06/2021 FOR MAIN HOUSE: |
| | |
| | 1- ITEM A3 ON PAGE 1 OF 6 IS INCORRECT. THIS ITEM IS |
| | ASKING FOR THE PROPERTY DESCRIPTION. FORM SUBMITTED |
| | SAYS 1B. WHAT IS 1B? REVISE AS REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH |
| | FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS |
| | REQUIRED TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT SHOWN ON |
| | ITEM C2(E) DOESN'T MATCH ELEVATION SHOWN ON SURVEY |
| | SUBMITTED. REVISE AS REQUIRED. |
| | NOTE: CLARIFY WHAT ARE THE ELEVATIONS 7.40', 7.45' AND |
| | 7.44' SHOWN ON THE SURVEY NEXT TO THE A/C PADS?. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- ELEVATION OF LOWEST MACHINERY OR EQUIPMENT DOESN'T |
| | MEET THE CITY FREEBOARD REQUIREMENT OF 1 FOOT ABOVE THE |
| | BASE FLOOD ELEVATION AS REQUIRED BY CITY ORDINANCE |
| | 4658-16. |
| | EQUIPMENT NEEDS TO BE RAISED AND ELEVATION CERTIFICATE |
| | NEEDS TO BE REVISED ACCORDINGLY. |
| | NOTE: ORIGINAL PLANS WERE APPROVED BEFORE THE NEW FLOOD |
| | MAPS TOOK EFFECT. PREVIOUS MAPS WERE BASED ON NGVD 1929 |
| | ELEVATION DATUM. BASED ON NGVD, THE BASE FLOOD |
| | ELEVATION WAS 7 FEET AND THE REQUIRED FINISHED FLOOR |
| | ELEVATION WAS 8 FEET NGVD. |
| | |
| | 5- COMMENTS ON SECTION D ON PAGE 2 OF 6 SPECIFIES A/C |
| | EQUIPMENT PAD LOCATED EASTERLY SIDE OF HOUSE. BASED ON |
| | SURVEY SUBMITTED, THIS IS INCORRECT. REVISE AS |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 6- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM |
| | C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED |
| | BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS. |
| | PROVIDE SURVEY SHOWING THOSE ELEVATIONS. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 7- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO |
| | BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION. |
| | SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019 |
| | EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY |
| | THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND |
| | SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED |
| | 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE |
| | BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT |
| | PHOTOS. |
| | NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE |
| | AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE |
| | YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF |
| | CERTIFICATION. |
| | |
| | |
| | COMMENTS FOR ELEVATION CERTIFICATE CERTIFIED ON |
| | 05/06/2021 FOR GARAGE: |
| | |
| | 1- REVISE/CLARIFY DESCRIPTION ON ITEM A4 ON PAGE 1 OF |
| | 6. WHAT IS A "DEATTACHED GARAGE"?. REVISE/CLARIFY AS |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- ITEM A7 ON PAGE 1 OF 6 IS INCORRECT. THERE IS NOT |
| | CRAWLSPACE IN THE GARAGE. REVISE AS REQUIRED. |
| | SEC. 107..2.1 CITY AMENDMENTS. |
| | |
| | 3- SQUARE FOOTAGE SPECIFIED ON ITEM A8(A) ON PAGE 1 OF |
| | 6 IS INCORRECT. ACCORDING TO SURVEY SUBMITTED THE |
| | GARAGE SQUARE FOOTAGE IS 733 S.F. NOT 586 S.F. REVISE |
| | AS REQUIRED. NOTE: SQUARE FOOTAGE IS TAKEN FROM |
| | EXTERIOR WALLS. |
| | SEC. 107..2.1 CITY AMENDMENTS. |
| | |
| | 4- TOTAL NET AREA OF FLOOD OPENINGS SPECIFIED ON ITEM |
| | A8(C) ON PAGE 1 OF 6 IS INCORRECT. SURVEYOR PROVIDED |
| | COMMENT AT BOTTOM OF SECTION D STATING "VENTING BASED |
| | ON FLOOD SOLUTIONS VENTS FS 1412 PER CLIENTS". |
| | ACCORDING TO ENGINEERED VENT PRODUCT APPROVAL FL17588 |
| | SUBMITTED WITH PERMIT APPLICATION #16061174 THE |
| | SELECTED VENT FS-1412 HAS A NET FREE AREA OF 106.7 SQ. |
| | IN. PER VENT. IF THERE ARE 5 VENTS, THEN THE TOTAL NET |
| | AREA IS 533.5 SQ. IN. NOT 1000 SQ. IN. REVISE AS |
| | REQUIRED. NOTE: COORDINATE WITH ITEM #5 BELOW. |
| | SEC. 107..2.1 CITY AMENDMENTS. |
| | |
| | 5- BASED ON ITEMS #3 AND #4 ABOVE IT LOOKS LIKE THE |
| | ENGINEER OF RECORD FOR PERMIT #16061174 NEEDS TO REVISE |
| | THE PLANS AND NUMBER OF REQUIRED FLOOD VENTS. SHEET A-2 |
| | SPECIFIES A GARAGE AREA OF 586 S.F. ALSO, ENGINEER |
| | SHOWS 5 FLOOD VENTS (MODEL FS-1412 PRODUCT APPROVAL |
| | FL17588) ON WEST AND EAST WALLS. |
| | ENGINEER OF RECORD NEEDS TO PROVIDE CORRECT GARAGE |
| | SQUARE FOOTAGE AND REVISE THE NUMBER OF REQUIRED VENTS. |
| | SUBMIT REVISE PLANS FOR REVIEW. REVISION FEES APPLY. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | NOTE: SQUARE FOOTAGE IS TAKEN FROM EXTERIOR WALLS. |
| | |
| | 6- ITEM C2(A) SHOWN ON PAGE 2 OF 6 DOESN'T MATCH FINISH |
| | FLOOR ELEVATION SHOWN ON SURVEY SUBMITTED. REVISE AS |
| | REQUIRED TO MATCH. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 7- ITEM C2(B) SHOWN ON PAGE 2 OF 6 IS INCORRECT. THERE |
| | IS NOT NEXT HIGHER FLOOR IN THE GARAGE. REVISE AS |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 8- ITEM C2(F) LOWEST ADJACENT GRADE AND ITEM |
| | C2(G)HIGHEST ADJACENT GRADE SHOWN CAN NOT BE VERIFIED |
| | BECAUSE SURVEY SUBMITTED DOESN'T SHOW THIS ELEVATIONS. |
| | PROVIDE SURVEY SHOWING THOSE ELEVATIONS. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 9- PHOTOS SHOWN ON PAGES 5 OF 6 AND PAGE 6 OF 6 NEED TO |
| | BE TAKEN WITHIN 90 DAYS FROM THE DATE OF CERTIFICATION. |
| | SEE FEMA ELEVATION CERTIFICATE INSTRUCTIONS (2019 |
| | EDITION). THIS ELEVATION CERTIFICATE WAS CERTIFIED BY |
| | THE SURVEYOR ON 05/06/2021 WHEN THE EMBOSSED SEAL AND |
| | SIGNATURE WAS APPLIED. THE PHOTOS PROVIDED ARE DATED |
| | 04/03/2020 AND IT LOOKS LIKE THEY WERE TAKEN WHEN THE |
| | BUILDING WAS UNDER CONSTRUCTION. PROVIDE CURRENT |
| | PHOTOS. |
| | NOTE: ALSO, REVISE THE DATE SHOWN BY THE BOTTOM MIDDLE |
| | AREA OF SECTION D. IT SAYS 4/3/2020. THIS DATE IS ONE |
| | YEAR OLD. IT SHOULD BE THE SAME DATE AS DATE OF |
| | CERTIFICATION. |
| | |
| | |
| | REVISE SURVEY SUBMITTED: |
| | |
| | 1- SURVEY SUBMITTED IS AN SPECIFIC PURPOSE |
| | SURVEY-"NORTHERLY FORMBOARDTIE IN". SEE TOP OF SURVEY. |
| | IF THIS SURVEY IS FOR ELEVATION CERTIFICATE FINISHED |
| | CONSTRUCTION, THEN THE SURVEY SHOULD BE A FINAL SURVEY |
| | AS WELL NOT A FORMBOARD SURVEY. PROVIDE FINAL SURVEY. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 2- FLOOD ZONE INFORMATION SPECIFIED AT THE BOTTOM |
| | MIDDLE OF SHEET IS OLD. THE CURRENT FLOOD MAP WENT INTO |
| | EFFECT ON 10/05/2017. REVISE ALL FLOOD INFORMATION AS |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- SURVEY DOESN'T MATCH APPROVED PLANS AND PHOTOS SHOWN |
| | ON THE ELEVATION CERTIFICATES. THERE IS A BREEZEWAY |
| | CONNECTING THE GARAGE TO THE MAIN HOUSE. REVISE AS |
| | REQUIRED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE REVISED SURVEY WITH SURVEYORS ORIGINAL |
| | SEAL/SIGNATURE AS REQUIRED BY CHAPTER 472 F.S. WHEN |
| | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | NOTE: THIS CAN BE ACHIEVED BY UPLOADING DOCUMENTS WITH |
| | SURVEYOR'S DIGITAL SIGNATURE OR BY PROVIDING HARD COPY |
| | PLANS/DOCUMENTS WITH SURVEYOR'S ORIGINAL |
| | SEAL/SIGNATURE. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |